Description
Littelfuse® Ground Fault Monitor, Series: SE-701, 24 V AC, 0 to 5 V DC Analog Output, Isolated NO (1 Form A), NC (1 Form B) Output Contact, 24 to 12 AWG Wire Clamping Terminal, DIN Rail Mount, 3 in H x 2.2 in W x 4.5 in D
Features:
- Adjustable pickup (1 to 99%) trip setting based on input CT primary, allows use with any CT, minimum 50 mA with EFCT series
- Adjustable time delay (50 ms to 2.5 s) - adjustable trip delay allows quick protection and system coordination
- Form A and form B ground fault output contacts for operation of separate annunciation and trip circuits
- Analog output (0 to 5 VDC) allows for connecting an optional meter (PGA-0500) or a control system
- CT-loop monitoring - alarms when CT is not connected
- Selectable DFT or peak detection filtering compatible with variable-speed drives
- Harmonic filtering eliminates nuisance tripping
- Non-volatile trip memory retains trip state when de-energized to simplify troubleshooting
- No calibration required, saves on maintenance cost
- Universal power supply allows operation in application where one side of PT is faulted, provides flexibility for numerous applications
Standards/Approval:
- cCSAus File No. LR53428
- UL File No. E340889
- CE Certified
- C-Tick N11659
- FCC Approved
- PPROP65: This product can expose you to chemicals including nickel, which is known to the State of California to cause cancer
Warranty:
5 Years