Description
EATON Ventilated Transformer, Type K-4 K-Factor Non-Linear, 480 V Primary, 208Y/120 V Secondary, 75 kVA Power, 60 Hz Frequency, 3 ph, 2 at +2.5%/4 at -2.5% Taps, Wall Mounting, 220 deg C Insulation, NEMA 2 Enclosure, 80 deg C, 31-1/2 in L x 34-1/2 in W x 51 in H Dimensions
Features:
- Includes transformers with DOE 2016 and NEMA TP-1 efficiency requirements and transformers with other efficiency requirements
- Specially designed to withstand the harmful overheating effects caused by harmonics generated by nonlinear (non-sinusoidal) loads
- Neutral bus size configured to accommodate at least 200% of the rated current compensates for increased neutral currents found in non-linear loads, thus reducing heat
- Electrostatic shield reduces transient noise in the system which may affect sensitive computer loads
- Transformers include a versatile bonding/grounding bar affixed to the bottom panel as standard, to provide compliance with NEC 450.10(A)
- Uses WS60 weather shield
- Aluminum winding
- Certified test report of standard production tests for the specific serial number to be shipped
- Low sound design, LS47 indicates low sound equal to 47 dB
- Certified sound level report
- DOE 2016 energy-efficient transformer
Standards/Approval:
- UL Listed,DOE2016 Efficient
Warranty:
1 year