KSCdirect

Product Data

KSCdirect Part #: HON W7080A1016/U
Description: MLTIZN LMT ANALYZER
MFG Part #: W7080A1016/U
UPC: 85267116404
Supplier: HONEYWELL
Variable lead time item; we expect to ship this promptly.
You will be notified of any delay and may cancel at that time.

Your Price: $2436.61 / EA

QTY:  
For shipping rates, add item to cart.
* Quantity discounts may be available. Call Kelly Supply at 800-918-8939.
Alternatively, you may e-mail info@kscdirect.com for service.

Details

The Honeywell W7080A1016/U MLTIZN LMT Analyzer is a high-performance monitoring device designed for precise measurement and analysis in various applications. This analyzer features advanced technology for accurate data collection and reporting, ensuring compliance with industry standards. Its compact design allows for easy installation in tight spaces, while robust materials ensure durability and reliability. The device supports multiple interfaces for seamless integration into existing systems, making it ideal for both new installations and upgrades. With a focus on efficiency and accuracy, the W7080A1016/U is a top choice for professionals seeking reliable performance.


Commercial Building Controls : Building Management Systems : Controllers (Legacy) : W7080 : W7080A1016/U

Load Analyzer, 3 Heat/ 3 Cool

Overview

Controls heating, cooling and space demand oriented economizer operation in the Honeywell Electronic Dual Set point Multizone control system.

Features

  • Controls 3 stages of on/off heating, modulated heating, modulated economizer, 3 stages of on/off cooling and modulated cooling.
  • Responds to highest heating and cooling demand signal from up to 12 T7080 Zone Thermostat/Transmitters.
  • Analyzer is short-circuit protected source of 24 Vdc power for zone thermostat/transmitter, sensor and W7081A Limit Controller Package.
  • Switches all stages off when power is interrupted; switches stages on when power is restored.
  • Compressor turn-on time delays must be incorporated for each compressor.
  • No adjustment or calibrations required.
  • Night setback and cooling shutdown for individual or all zones by addition of time-clock.
  • Mounts with 4 No. 8 Screws (not provided) through holes in base.

Product Specifications

Application
Packaged RTU; Furnace; Split System
Dimensions (in.)
6 1/4 in. high x 4 1/8 in. wide x 2 5/16 in. deep
Dimensions (mm)
159 mm high x 105 mm wide x 59 mm deep
Comments
Load analyzer provides control of On/Off and modulated cooling and modulated economizer functions
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
Component Recognized
Approvals, CSA
Component Recognized
Electrical Connections
1/4 in. quick-connect male terminals
Application Size
3 Heat / 3 Cool
Control System
W7080 control system
Compatible With
T7080 Thermostat
Contact Ratings
NO 240 VA inrush @ 24 Vac, 60 VA running @ 24 Vac; NC 75 VA inrush @ 24 Vac, 30 VA running @ 24 Vac
Voltage
24 Vdc
Operating Temperature Range (F)
-40 F to +150 F
Operating Temperature Range (C)
-40 C to +65 C
Shipping and Storage Temperature Range (F)
-40 F to +150 F
Shipping and Storage Temperature Range (C)
-40 C to +65 C
Approvals, Department of Defense Guidelines
Meets
Approvals, ASHRAE Guidelines
Meets ASHRAE 90-75

Attributes/Specifications

Category Commercial Building Controls
Manufacturer HONEYWELL
Product Building Management Systems
Style Building Management Systems

Supplemental Files