The Pneu Thermostat 60 - 90F from NEUCO INC is designed for precise temperature control in pneumatic systems. This thermostat features a reliable operating range of 60 to 90 degrees Fahrenheit, ensuring optimal performance in various environments. Its durable construction meets industry standards for safety and efficiency, making it suitable for both residential and commercial applications. Easy to install and operate, this thermostat enhances system efficiency and contributes to maintaining comfortable indoor conditions.
Commercial Building Controls : Pneumatic Products : Pneumatic Thermostats : TP970 : TP970B2002/U
Pneumatic Thermostat Reverse Acting,Cool
Overview
Pneumatic thermostat gives comparable control of pneumatic valves and damper actuators in heating & air conditioning systems. Replacement kits available for Johnson, Powers, Robertshaw, Barber-Colman, and past Honeywell 2-pipe pneumatic thermostats.
Features
- Honeywell's best pneumatic thermostat-TP970 series.
- Shock-resistant, suspension-mounted thermostats provide dependable performance and responsiveness year in and year out.
- Pilot operated for high capacity.
- Direct Acting (DA) and Reverse Acting (RA) models are available.
- Wide throttling range models for Zero Energy Band (ZEB) operation are available.
- Adapter plate in Convertastat and Modernization kits covers existing thermostat wall mark.
- Backplate has molded air connections-no separate fittings needed.
- Universal locking cover with satin chrome finish and horizontal, vertical, or blank window options.
- Typical Wide Throttling Range Application.
Product Specifications
- Application
- Cooling only systems
- Airflow Usage
- 0.011 scfm (5.2 mL/s)
- Dimensions (in.)
- 3 1/4 in. high x 2 in. wide x 1 5/8 in. deep
- Dimensions (mm)
- 83 mm high x 51 mm wide x 41 mm deep
- Maximum Safe Operating Pressure (psi)
- 25 psi
- Maximum Safe Operating Pressure (kPa)
- 170 kPa
- Temperature Range (F)
- 100 F maximum
- Includes
- Order Cover Separately
- Mounting
- Wall mount
- Approvals, Underwriters Laboratories Inc.
-
- Approvals, CSA
-
- Setpoint Temperature Range (F)
- 59 F to 90 F
- Shipping and Storage Temperature Range (F)
- 150 F maximum
- Shipping and Storage Temperature Range (C)
- 66 C maximum
- Approvals, Factory Mutual
-
- Sensor Element
- Bimetal
- Throttling Range (F)
- 2 F to 10 F (factory set 4 F)
- Throttling Range (C)
- -16 C to -12 C (factory set -15 C)
- Connection Size (in.)
-
- Differential Pressure Range (psi)
-
- Differential Pressure Range (kPa)
-
- Approvals, NEMA Standard
-
- Action
- Reverse Acting
- Setpoint
- Single
- Number of Pipes
- 2
- Changeover Pressure (psi)
-
- Changeover Pressure (kPa)
-
- Mainline Pressure Range (psi)
-
- Capacity
-
- Control Range (fpm)
-
- Control Range (m/s)
-
- Number of Sensor Inputs
-
- Remote Control Point Adjustment
-
- Approximate Throttling Range, Midscale (psi)
-
- Approximate Throttling Range, Midscale (kPa)
-