The HONEYWELL TP9610A1006/U thermostat is designed for precise temperature regulation in HVAC systems. This user-friendly device allows for easy temperature adjustments, ensuring optimal comfort in any environment. Its compact design fits well in various settings, while its advanced technology guarantees accurate readings and efficient operation. Compatible with a wide range of heating and cooling systems, this thermostat enhances energy efficiency and comfort, making it an essential component for both residential and commercial applications.
Commercial Building Controls : Pneumatic Products : Pneumatic Thermostats : TP9610 : TP9610A1006/U
Pneumatic Thermostat Dir.Act., Wall, D/N
Overview
TP9610 Pneumatic thermostat, for proportional control of pneumatic valves and actuators with one/two-pipe systems, is not only affordable and easy to install, but it controls temperature with Honeywell reliability. Available with two cover options.
Features
- Redesigned models fit your high-volume pneumatic applications.
- Backplate mounts quickly.
- Thermostat snaps onto backplate.
- Cover is mounted and locked into place with concealed setscrews.
- Attractive Euro-contoured design comes with choice of two cover options.
- Neutral taupe color blends with todays commercial interiors.
- Adapter kits are available to retrofit most pneumatic jobs.
- Branch line capacity High for TP9600, TP9610, TP9603, TP9620.
Product Specifications
- Application
- Wall Thermostat, Day/Night operation
- Airflow Usage
- 0.011 scfm (5.2 mL/s)
- Dimensions (in.)
- 3 1/4 in. high x 2 in. wide x 1 5/8 in. deep
- Dimensions (mm)
- 83 mm high x 51 mm wide x 41 mm deep
- Maximum Safe Operating Pressure (psi)
- 25 psi
- Maximum Safe Operating Pressure (kPa)
- 170 kPa
- Temperature Range (F)
- 50 F to 100 F
- Temperature Range (C)
- 10 C to 38 C
- Includes
- Cover, Setpoint, and Thermometer are Visible
- Mounting
- Vertical Wall Mounting
- Approvals, Underwriters Laboratories Inc.
-
- Approvals, CSA
-
- Setpoint Temperature Range (C)
- Day: 15 C to 30 C, Night: 10 C to 27 C
- Setpoint Temperature Range (F)
- Day: 59 F to 90 F, Night: 50 F to 75 F
- Shipping and Storage Temperature Range (F)
- 150 F maximum
- Shipping and Storage Temperature Range (C)
- 66 C maximum
- Approvals, Factory Mutual
-
- Sensor Element
- Bimetal
- Throttling Range (F)
- 2 F to 10 F
- Throttling Range (C)
- 1 C to 5 C
- Connection Size (in.)
-
- Differential Pressure Range (psi)
-
- Differential Pressure Range (kPa)
-
- Approvals, NEMA Standard
-
- Action
- Direct Acting
- Air connections
- Barb fittings 5/32 in. (4 mm)
- Setpoint
- Day/Night
- Number of Pipes
- 2
- Changeover Pressure (psi)
- Day 13 psi, Night 18 psi
- Changeover Pressure (kPa)
- Day 90 kPa, Night 124 kPa
- Mainline Pressure Range (psi)
-
- Capacity
-
- Control Range (fpm)
-
- Control Range (m/s)
-
- Number of Sensor Inputs
-
- Remote Control Point Adjustment
-
- Approximate Throttling Range, Midscale (psi)
-
- Approximate Throttling Range, Midscale (kPa)
-