The Honeywell T678D1020 Temperature Controller is designed for precise temperature management in HVAC and industrial applications. Its user-friendly interface allows for easy programming and monitoring, ensuring optimal performance. This controller is built to handle a wide range of temperatures, making it versatile for various environments. Its compact design facilitates installation in tight spaces, while its robust construction ensures durability. Ideal for maintaining consistent temperature levels, this controller enhances system efficiency and user comfort.
Commercial Building Controls : Standalone Controllers : Temperature Controllers : T678 : T678D1020/U
Remote Temp Control, 55F-90F Range, 2 SPDT, Copper Bulb, 5.5 ft. Capillary, Switch: 2F Fixed/Interstage: 2F Diff.
Overview
Remote bulb thermostats regulate temperature of air or liquids in ducts, pipes, tanks and boilers.
Features
- Suitable for applications requiring temperature control of air or liquids where controller must be placed outside the sensing area.
- Typical uses include control of dampers and valves in heating, cooling and heating-cooling systems.
- Fast response models (available for use in return air duct) operate approximately four times faster than standard models.
- Controller can be mounted in any position. Ambient temperature compensation provides good temperature control.
- Refer to T775 Electronic Remote Temperature Controller where more exact control is required and/or remote controller location is preferred.
- T678 models have a maximum connected load of 2000 VA.
Product Specifications
- Hazmat Information
- UN1294 Toluene
- Application
- Control of dampers and valves in heating, cooling or heating-cooling systems
- Dimensions (in.)
- 5 5/8 in. high x 2 in. wide x 2 5/8 in. deep
- Dimensions (mm)
- 143 mm high x 51 mm wide x 67 mm deep
- Item Type
- Product
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Listed: E4436, Vol. 4, Guide XAPX
- Approvals, CSA
- Certified: File No. LR95329-1
- Contact Ratings
- 120 Vac-- 8.0 AFL, 48.0 ALR; 240 Vac-- 5.1 AFL, 30.6 ALR
- Voltage
- 120 Vac; 240 Vac
- Setpoint Temperature Range (F)
- 55 F to 90 F
- Operating Temperature Range (F)
- 130 F Maximum
- Operating Temperature Range (C)
- 54 C Maximum
- Output
- relay
- Relay Outputs
- 2 SPDT switch contacts
- Sensor Inputs
- 1
- Sensor Element
- Copper bulb
- Capillary Length (ft)
- 5 1/2 ft
- Capillary Length (m)
- 1.7 m
- Bulb Size (in.)
- 5/16 in. x 11 11/16 in.
- Bulb Size (mm)
- 8 mm x 297 mm
- Differential Temperature (F)
- 2 F
- Differential Temperature (C)
- 1.8 C
- Interstage Differential Temperature (C)
- 1.1 C
- Interstage Differential Temperature (F)
- 2 F