KSCdirect

Product Data

KSCdirect Part #: HON T675A1706/U
Description: TEMP CONTROLLER
MFG Part #: T675A1706/U
UPC: 85267090452
Supplier: HONEYWELL
Variable lead time item; we expect to ship this promptly.
You will be notified of any delay and may cancel at that time.

Your Price: $162.00 / EA

QTY:  
For shipping rates, add item to cart.
* Quantity discounts may be available. Call Kelly Supply at 800-918-8939.
Alternatively, you may e-mail info@kscdirect.com for service.

Details

The HONEYWELL Temp Controller is designed for precise temperature management in various applications. This controller features advanced technology for accurate readings and reliable performance. Its compact design allows for easy installation in tight spaces. Built with high-quality materials, it ensures durability and compliance with industry standards. Ideal for HVAC systems, refrigeration, and industrial processes, this temperature controller enhances efficiency and ensures optimal performance.


Commercial Building Controls : Standalone Controllers : Temperature Controllers : T675A,B : T675A1706/U

Remote Temp Control, 0F-100F Range, 1 SPDT, 5 ft. Capillary, 3F-10F Diff., Fast Response Model

Overview

Remote bulb thermostats regulate temperature of air or liquids in ducts, pipes, tanks and boilers.

Features

  • Suitable for applications requiring temperature control of air or liquids where controller must be placed outside the sensing area.
  • Typical uses include control of dampers and valves in heating, cooling and heating-cooling systems.
  • Fast response models (available for use in return air duct) operate approximately four times faster than standard models.
  • Controller can be mounted in any position.
  • Ambient temperature compensation provides good temperature control.
  • Refer to T775 Electronic Remote Temperature Controller where more exact control is required and/or remote controller location is preferred.
  • T675A models with fixed differential have an electrical rating of 125 VA at 120/208/240 and 277 Vac.
  • T675B models have 125 VA pilot duty up to 277 Vac.
  • T678 models have a maximum connected load of 2000 VA.

Product Specifications

Hazmat Information
UN 1993 Flammable liquid, n.o.s.
Application
Regulates temperature of air or liquids in ducts, pipes, tanks and boilers
Dimensions (in.)
5 5/8 in. high x 2 in. wide x 2 5/8 in. deep
Dimensions (mm)
143 mm high x 51 mm wide x 67 mm deep
Includes
131524A duct bulb holder
Comments
Fast response model, includes 107324A Duct Bulb Holder
Item Type
Product
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
UL Listed: E4436, Vol. 4, Sec. 11, Guide XAPX
Approvals, CSA
CSA Listed: Report -1
Tradeline Value
Tradeline
Contact Ratings
120 Vac-- 8.0 AFL, 48.0 ALR; 240 Vac-- 5.1 AFL, 30.6 ALR; 277 Vac--4.2 AFL, 25.2 ALR
Voltage
120 Vac or 240/277 Vac
Setpoint Temperature Range (C)
-18 C to +38 C
Setpoint Temperature Range (F)
0 F to 100 F
Operating Temperature Range (F)
125 F Maximum
Operating Temperature Range (C)
52 C Maximum
Type
Remote bulb
Output
relay
Relay Outputs
1 SPDT
Sensor Inputs
1
Sensor Element
Fast response capillary
Capillary Length (ft)
5 ft
Capillary Length (m)
1.5 m
Bulb Size (in.)
coil 1 1/2 in. diameter x 5 in.
Bulb Size (mm)
coil 38.1 mm x 127 mm
Differential Temperature (F)
3 F to 10 F
Differential Temperature (C)
1.7 C to 5.6 C

Attributes/Specifications

Category Commercial Building Controls
Manufacturer HONEYWELL
Product Standalone Controllers
Style Standalone Controllers

Supplemental Files