The Thermostat from NEUCO INC is designed for precise temperature regulation in HVAC systems. This device features a user-friendly interface and reliable performance, ensuring optimal comfort in residential and commercial environments. Its compact design allows for easy installation and integration into existing systems. The thermostat is compatible with various heating and cooling applications, making it a versatile choice for temperature control. Built with high-quality materials, it guarantees durability and long-lasting functionality.
Commercial Building Controls : Standalone Controllers : Temperature Controllers : T4031 : T4031C1012/U
Remote Temperature Controller, 40F to 180F Set Point, 5F Differential, 1 SPDT Break on Temperature Rise, Copper Bulb, 5.5 ft. Capillary
Overview
Ambient temperature compensated, high-limit controllers for HVAC, agriculture, and industrial applications.
Features
- Suitable for line-voltage, low voltage, or millivolt (PowerPile) control of bulk milk tanks, beverage dispensing machines, ice cube machines, dishwashers, crop drying, tobacco curing, and similar applications.
- Enclosed snap action switches available with SPST or SPDT action.
- Models available that make or break on temperature rise.
- Screwdriver adjustment for temperature setting; external knob option.
- Immersion well not included.
Product Specifications
- Hazmat Information
- UN1294 Toluene
- Application
- Line-voltage, low-voltage or millivolt (Powerpile) control of bulk milk tanks, beverage dispensing machines, ice cube machines, dishwashers, crop drying, tobacco curing and similar applications.
- Dimensions (in.)
- 5 5/8 in. high x 2 in. wide x 2 1/8 in. deep
- Dimensions (mm)
- 143 mm high x 51 mm wide x 54 mm deep
- Comments
- Break on temperature rise
- Item Type
- Product
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- Component Recognized
- Approvals, CSA
- Listed
- Contact Ratings
- 120 Vac-- 8.0 AFL, 48.0 ALR; 240 Vac-- 5.1 AFL, 30.6 ALR
- Voltage
- 120 Vac; 240 Vac
- Setpoint Temperature Range (C)
- 4 C to 82 C
- Setpoint Temperature Range (F)
- 40 F to 180 F
- Operating Temperature Range (F)
- 205 F Maximum
- Operating Temperature Range (C)
- 96 C Maximum
- Type
- Remote bulb
- Output
- relay
- Relay Outputs
- 1 SPST, break on temperature rise
- Sensor Inputs
- 1
- Sensor Element
- Copper
- Capillary Length (ft)
- 5 1/2 ft
- Capillary Length (m)
- 1.7 m
- Bulb Size (in.)
- 2 7/8 in. long x 3/8 in. diameter
- Bulb Size (mm)
- 73 mm long x 10 mm diameter
- Differential Temperature (F)
- 5 F
- Differential Temperature (C)
- 2.8 C