The RP970A1008/U is a VENTILE V5825, featuring a DN32 size with G 1 1/2 inch x 32mm connections. This valve by NEUCO INC is designed for efficient flow control in industrial applications. Its robust construction ensures durability and resistance to corrosion, making it suitable for various fluids. The valve complies with industry standards, providing reliable performance and easy integration into existing systems.
Commercial Building Controls : Pneumatic Products : Pneumatic Relays : RP970 : RP970A1008/U
Wall, In-Line or panel mounted Pneumatic Capacity Relay
Overview
Direct acting, modulating relay provides increased capacity of the branchline pressure to the final control device. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices.
Features
- In-line, wall, or panel mounted.
- Sharp-barb air connections.
- Molded plastic construction with neoprene diaphragms.
- Mounting clip provided.
Product Specifications
- Application
- Pneumatic Capacity Relay
- Airflow Usage
- 0.002 scfm (1.0 mL/s) maximum
- Dimensions (in.)
- 1 1/2 in. diameter, 1 1/2 in. deep
- Dimensions (mm)
- 38 mm dia., 38 mm deep
- Maximum Safe Operating Pressure (psi)
- 30 psi, maximum
- Maximum Safe Operating Pressure (kPa)
- 205 kPa, maximum
- Temperature Range (F)
- 0 F to 140 F
- Temperature Range (C)
- -18 C to +60 C
- Includes
- 14003030-001, 1 1/2 in. Mounting Clip for Mounting relay to wall or panel
- Mounting
- Wall or In-line or panel
- Operating Humidity Range (% RH)
- 5 to 95% RH
- Pressure Range (psi)
- Input Operating--0 to 20 psi
- Pressure Range (kPa)
- Input Operating--0 to 138 kPa
- Action
- Direct Acting
- Air connections
- Barb fittings, Port 1: 1/4 in. (6 mm) O.D. plastic tubing; Other Ports: 5/32 in. (4 mm) O.D. plastic tubing
- Capacity
- 0.039 scfm at 1 psi differential (18 mL/s at 5 kPa differential)
- Operation
- Provides increased capacity of branchline pressure to final control device