The Honeywell NXBK0400CS30000000 is a 40HP NXS VFD CoolBlue drive, specifically designed for 208V 3-phase applications. This variable frequency drive offers advanced control capabilities, enhancing motor performance while reducing energy consumption. Its compact design allows for easy installation in various settings, making it suitable for HVAC systems and industrial applications. The CoolBlue technology ensures efficient cooling, prolonging the lifespan of the drive. With robust features and compliance with industry standards, this VFD is an excellent choice for optimizing motor control.
Commercial Building Controls : Variable Frequency Drives : General Purpose Drives : NXS Drive with Cool Blue Bypass : NXBK0400CS30000000
40HP NXS VFD, COOLBLUE DRIVE ONLY
Overview
Variable Frequency Drives (VFD) accept a control input and then output tailored PWM control signal to operate (motors, fans, pumps, etc.) with maximum efficiency. The VFD can be field-programmed without any extra devices or computer connections.
Features
- Seven configurable applications built in.
- Easy commissioning through software or control panel.
- Devices can be wall-mounted or panel-mounted.
- Eleven protective functions (see Form 63-2600, Users Manual, Technical Data sections).
- Insulated gate bi-polar transistor (IGBT) technology.
- Modbus, BacNet, Device Net, Profibus, LobBus, NS available as options cards.
Product Specifications
- Dimensions (in.)
- 48H x 12D x 36W
- Dimensions (mm)
- 1176H x 294D x 882W
- Weight (lb)
- 193 lb
- Weight (kg)
- 424.6 kg
- Item Type
- Product
- Frequency
- 0 Hz to 320 Hz
- Voltage
- 208 Vac
- Operating Temperature Range (F)
- High Overload 14 to 122; Low Overload 14 to 104
- Operating Temperature Range (C)
- High Overload -10 to 50; Low Overload -10 to 40
- Enclosure
- NEMA 3R
- Relay Outputs
- 24 Vdc/8A; 125 Vdc/0.4A; 250 Vac/8A
- Horsepower
- 40 HP
- Current Ratings
- 114A
- Analog Current Output
- 0 (4) - 20 mA, max 500 ohm
- Bypass
- Drive alone
- Auto Bypass
- No
- Drive Family
- NXS
- Disconnect Type
- No Disconnect
- Pilot Lights
- No
- Control Transformer
- No
- Drive Input Disconnect
- No
- Drive Input Fuses
- No
- Type of RFI Filter
- Industrial filter
- Continuous Output Current
- overload 1.5 x High overload current (1min/10min); overload 1.1 x Low overload current (1min/10min)
- Starting Torque
- 200% High; 150% Low
- Peak Current
- 2 x high overload current, 2 seconds every 20 seconds
- Acceleration time
- 0 - 3000 sec
- Deceleration time
- 0 - 3000 sec
- Analog Voltage Input
- 0 - 10 Vdc , 200K ohm
- Analog Current Input
- 0 (4) - 20 mA, 250 ohm differential
- Digital Output
- 50 mA/48v open collector
- Reference Output Voltage
- +10V, +3%, max 10mA
- Auxiliary Voltage
- 24V, 15%, max 250 mA
- Frame Type
- FR7
- Layout
- Vertical