The HONEYWELL VFD BYPASS 230V 75HP (Model: HVFDSB3B0750G230/U) is designed for efficient motor control in industrial applications. This variable frequency drive (VFD) bypass system operates at 230 volts and supports motors up to 75 horsepower. It features a robust design compliant with NEMA 3R standards, ensuring durability in various environments. The unit is equipped with three contactors for reliable operation and easy integration into existing systems. Ideal for HVAC and process control applications, this VFD bypass enhances energy efficiency while providing seamless motor operation.
Commercial Building Controls : Variable Frequency Drives : SmartVFD HVAC : SmartVFD Bypass : HVFDSB3B0750G230/U
SmartVFD BYPASS, 230VAC, 75 HP,NEMA 12 Enclosure, Three Contactor Bypass
Overview
The SmartVFD BYPASS is available in four configurations to meet your application needs: Disconnect Only, Two Contractor Bypass, Three Contractor Bypass, and Three Contractor with Auto-Bypass.
Features
- Provides an economical means of bypassing the VFD
- Freeze/Fire/Smoke Interlock
- Fused Disconnect on some models
- 3-Contactor bypass provides VFD isolation from power with motor running in BYPASS mode
- 3-Contactor bypass provides TEST position powers the VFD without sending power to the motor
- 3-Contactor Bypass with Auto-Bypass adds the control capabilities below to the standard three Contactor Bypass
Product Specifications
- Dimensions (in.)
- 40.5 x 60 x 14
- Dimensions (mm)
- 1028.7 x 1524 x 355.6
- Weight (lb)
- Contact Customer Care
- Weight (kg)
- Contact Customer Care
- Item Type
- Product
- Frequency
- 0 Hz to 320 Hz
- Voltage
- 230 Vac
- Operating Temperature Range (F)
- 14 F to 122 F
- Operating Temperature Range (C)
- -10 C to 50 C
- Enclosure
- NEMA 12
- Relay Outputs
- Max. switching load: 250Vac/2A or 250Vdc/0,4A
- Horsepower
- 75 HP
- Current Ratings
- 205 A
- Analog Current Output
- 0 (4) - 20 mA, max 500 ohm
- Bypass
- Drive with 3 contactor bypass
- Auto Bypass
- No
- Drive Family
- SmartVFD HVAC
- Contactor
- 3 Contactors
- Disconnect Type
- Fused
- Pilot Lights
- Yes
- Drive Input Disconnect
- Yes
- Drive Input Fuses
- Yes
- Type of RFI Filter
- EMC Filter
- Continuous Output Current
- overload 1.5 x High overload current (1min/10min); overload 1.1 x Low overload current (1min/10min)
- Starting Torque
- Depends on the Motor
- Acceleration time
- 0.1 - 3000 sec
- Deceleration time
- .1 - 3000 sec
- Analog Voltage Input
- 0 - 10 Vdc , 200K ohm
- Analog Current Input
- 0 (4) - 20 mA, 250 ohm differential
- Digital Output
- Open collector, max. load 48V/50mA
- Reference Output Voltage
- Maximum Load 10mA
- Auxiliary Voltage
- 20%, max. load 50 mA
- Frame Type
- 8