The Honeywell VFD Bypass 230V 60HP N12 3Cont FD AB is a high-performance solution designed for efficient motor control. This unit features a robust design suitable for 60HP applications, ensuring reliable performance in demanding environments. The NEMA 12 rating provides protection against dust and moisture, making it ideal for industrial settings. Its advanced bypass functionality allows for seamless transitions between VFD and direct operation, enhancing system flexibility. Constructed from durable materials, this VFD bypass meets industry standards, ensuring compliance and optimal performance in various applications.
Commercial Building Controls : Variable Frequency Drives : SmartVFD HVAC : SmartVFD Bypass : HVFDSB3B0600G231/U
SmartVFD BYPASS,230VAC, 60 HP,NEMA 12 Enclosure, Three Contactor Bypass with Auto Bypass
Overview
The SmartVFD BYPASS is available in four configurations to meet your application needs: Disconnect Only, Two Contractor Bypass, Three Contractor Bypass, and Three Contractor with Auto-Bypass.
Features
- Provides an economical means of bypassing the VFD
- Freeze/Fire/Smoke Interlock
- Fused Disconnect on some models
- 3-Contactor bypass provides VFD isolation from power with motor running in BYPASS mode
- 3-Contactor bypass provides TEST position powers the VFD without sending power to the motor
- 3-Contactor Bypass with Auto-Bypass adds the control capabilities below to the standard three Contactor Bypass
Product Specifications
- Dimensions (in.)
- 40.5 x 60 x 14
- Dimensions (mm)
- 1028.7 x 1524 x 355.6
- Weight (lb)
- Contact Customer Care
- Weight (kg)
- Contact Customer Care
- Item Type
- Product
- Frequency
- 0 Hz to 320 Hz
- Voltage
- 230 Vac
- Operating Temperature Range (F)
- 14 F to 122 F
- Operating Temperature Range (C)
- -10 C to 50 C
- Enclosure
- NEMA 12
- Relay Outputs
- Max. switching load: 250Vac/2A or 250Vdc/0,4A
- Horsepower
- 60 HP
- Current Ratings
- 170 A
- Analog Current Output
- 0 (4) - 20 mA, max 500 ohm
- Bypass
- Drive with 3 contactor bypass and Auto bypass
- Auto Bypass
- Yes
- Drive Family
- SmartVFD HVAC
- Contactor
- 3 Contactors
- Disconnect Type
- Fused
- Pilot Lights
- Yes
- Drive Input Disconnect
- Yes
- Drive Input Fuses
- Yes
- Type of RFI Filter
- EMC Filter
- Continuous Output Current
- overload 1.5 x High overload current (1min/10min); overload 1.1 x Low overload current (1min/10min)
- Starting Torque
- Depends on the Motor
- Acceleration time
- 0.1 - 3000 sec
- Deceleration time
- .1 - 3000 sec
- Analog Voltage Input
- 0 - 10 Vdc , 200K ohm
- Analog Current Input
- 0 (4) - 20 mA, 250 ohm differential
- Digital Output
- Open collector, max. load 48V/50mA
- Reference Output Voltage
- Maximum Load 10mA
- Auxiliary Voltage
- 20%, max. load 50 mA
- Frame Type
- 8