The HONEYWELL SMARTVFD BYPASS is designed for 230 VAC applications, providing a robust solution for 5 HP systems. This NEMA 1 rated unit ensures reliable performance in various environments. It features advanced bypass capabilities, allowing seamless transitions between VFD and direct line operation. Ideal for HVAC and industrial applications, it meets stringent compliance standards, ensuring safety and efficiency. The compact design facilitates easy installation and maintenance, making it a preferred choice for professionals.
Commercial Building Controls : Variable Frequency Drives : SmartVFD HVAC : SmartVFD Bypass : HVFDSB3B0050G130/U
SmartVFD BYPASS, 230 Vac,5 HP,Graphical, NEMA 1 Enclosure, Three Contactor Bypass
Overview
The SmartVFD BYPASS is available in four configurations to meet your application needs: Disconnect Only, Two Contractor Bypass, Three Contractor Bypass, and Three Contractor with Auto-Bypass.
Features
- Provides an economical means of bypassing the VFD
- Freeze/Fire/Smoke Interlock
- Fused Disconnect on some models
- 3-Contactor bypass provides VFD isolation from power with motor running in BYPASS mode
- 3-Contactor bypass provides TEST position powers the VFD without sending power to the motor
- 3-Contactor Bypass with Auto-Bypass adds the control capabilities below to the standard three Contactor Bypass
Product Specifications
- Dimensions (in.)
- 8.9 x 41.7 x 10.3
- Dimensions (mm)
- 226.06 x 1059.1 x 261.62
- Weight (lb)
- 55
- Weight (kg)
- 24.95
- Item Type
- Product
- Frequency
- 0 Hz to 320 Hz
- Voltage
- 230 Vac
- Operating Temperature Range (F)
- 14 F to 122 F
- Operating Temperature Range (C)
- -10 C to 50 C
- Enclosure
- NEMA 1
- Relay Outputs
- Max. switching load: 250Vac/2A or 250Vdc/0,4A
- Horsepower
- 5 HP
- Current Ratings
- 18A
- Analog Current Output
- 0 (4) - 20 mA, max 500 ohm
- Bypass
- Drive with 3 contactor bypass
- Auto Bypass
- No
- Drive Family
- SmartVFD HVAC
- Contactor
- 3 Contactors
- Disconnect Type
- Fused
- Pilot Lights
- Yes
- Drive Input Disconnect
- Yes
- Drive Input Fuses
- Yes
- Type of RFI Filter
- EMC Filter
- Continuous Output Current
- overload 1.5 x High overload current (1min/10min); overload 1.1 x Low overload current (1min/10min)
- Peak Current
- 2 x IN, 2 seconds every 20 second period
- Acceleration time
- 0.1 - 3000 sec
- Deceleration time
- .1 - 3000 sec
- Analog Voltage Input
- 0 - 10 Vdc , 200K ohm
- Analog Current Input
- 0 (4) - 20 mA, 250 ohm differential
- Digital Output
- Open collector, max. load 48V/50mA
- Reference Output Voltage
- Maximum Load 10mA
- Auxiliary Voltage
- 20%, max. load 50 mA
- Frame Type
- 5