The T675A1540/U Adjustable Differential Thermostat from NEUCO INC is designed for precise temperature control in HVAC applications. Operating within a range of 55 to 175°F, this thermostat features adjustable differential settings, ensuring optimal performance in various environments. Its robust construction and reliable performance make it suitable for both residential and commercial systems. The device complies with industry standards, ensuring compatibility with a wide range of heating and cooling systems. Ideal for maintaining desired temperature levels, it is a crucial component for efficient climate control.
Commercial Building Controls : Standalone Controllers : Temperature Controllers : T675A,B : T675A1540/U
Remote Temperature Controller, 55F to 175F Set Point, 1 SPDT, Copper Bulb, Includes 107324A Duct Bulb Holder
Overview
Remote bulb thermostats regulate temperature of air or liquids in ducts, pipes, tanks and boilers.
Features
- Suitable for applications requiring temperature control of air or liquids where controller must be placed outside the sensing area.
- Typical uses include control of dampers and valves in heating, cooling and heating-cooling systems.
- Fast response models (available for use in return air duct) operate approximately four times faster than standard models.
- Controller can be mounted in any position.
- Ambient temperature compensation provides good temperature control.
- Refer to T775 Electronic Remote Temperature Controller where more exact control is required and/or remote controller location is preferred.
- T675A models with fixed differential have an electrical rating of 125 VA at 120/208/240 and 277 Vac.
- T675B models have 125 VA pilot duty up to 277 Vac.
- T678 models have a maximum connected load of 2000 VA.
Product Specifications
- Application
- Regulates temperature of air or liquids in ducts, pipes, tanks and boilers
- Dimensions (in.)
- 5 5/8 in. high x 2 in. wide x 2 5/8 in. deep
- Dimensions (mm)
- 143 mm high x 51 mm wide x 67 mm deep
- Includes
- 107324A Duct Bulb holder
- Comments
- Includes 107324A Duct Bulb Holder
- Item Type
- Product
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Listed: E4436, Vol. 4, Sec. 11, Guide XAPX
- Approvals, CSA
- CSA Listed: Report -1
- Tradeline Value
- Tradeline
- Contact Ratings
- 120 Vac-- 8.0 AFL, 48.0 ALR; 240 Vac-- 5.1 AFL, 30.6 ALR; 277 Vac--4.2 AFL, 25.2 ALR
- Voltage
- 120 Vac or 240/277 Vac
- Setpoint Temperature Range (C)
- 13 C to 79 C
- Setpoint Temperature Range (F)
- 55 F to 175 F
- Operating Temperature Range (F)
- 200 F Maximum
- Operating Temperature Range (C)
- 93 C Maximum
- Type
- Remote bulb
- Output
- relay
- Relay Outputs
- 1 SPDT
- Sensor Inputs
- 1
- Sensor Element
- Copper bulb
- Capillary Length (ft)
- 5 ft
- Capillary Length (m)
- 1.5 m
- Bulb Size (in.)
- 1/2 in. x 3 9/16 in.
- Bulb Size (mm)
- 13 mm x 90 mm
- Differential Temperature (F)
- 3.6 F to 12 F
- Differential Temperature (C)
- 2 C to 6.7 C