KSCdirect

Product Data

KSCdirect Part #: HON T675A1532/U
Description: INSERTION THERMOSTAT
MFG Part #: T675A1532/U
UPC: 85267090414
Supplier: Approved Supplier
Usually ships in 1-2 days.
You will be notified of any delay and may cancel at that time.

Your Price: $325.00 / EA

QTY:  
For shipping rates, add item to cart.
* Quantity discounts may be available. Call Kelly Supply at 800-918-8939.
Alternatively, you may e-mail info@kscdirect.com for service.

Details

The INSERTION THERMOSTAT is engineered for accurate temperature measurement in HVAC systems. This device features a durable construction and is designed for easy installation in pipes or ducts. With a wide temperature range and high accuracy, it ensures optimal performance in various applications. The INSERTION THERMOSTAT is compatible with multiple control systems and meets industry standards for safety and reliability. Its compact design makes it suitable for both new installations and retrofits, providing a reliable solution for temperature control.


Commercial Building Controls : Standalone Controllers : Temperature Controllers : T675A,B : T675A1532/U

Remote Temp Control, 55F-175F Range, 1 SPDT, Copper Bulb, 5 ft. Capillary, 3.6F-12F Diff.

Overview

Remote bulb thermostats regulate temperature of air or liquids in ducts, pipes, tanks and boilers.

Features

  • Suitable for applications requiring temperature control of air or liquids where controller must be placed outside the sensing area.
  • Typical uses include control of dampers and valves in heating, cooling and heating-cooling systems.
  • Fast response models (available for use in return air duct) operate approximately four times faster than standard models.
  • Controller can be mounted in any position.
  • Ambient temperature compensation provides good temperature control.
  • Refer to T775 Electronic Remote Temperature Controller where more exact control is required and/or remote controller location is preferred.
  • T675A models with fixed differential have an electrical rating of 125 VA at 120/208/240 and 277 Vac.
  • T675B models have 125 VA pilot duty up to 277 Vac.
  • T678 models have a maximum connected load of 2000 VA.

Product Specifications

Hazmat Information
UN 1993 Flammable liquid, n.o.s.
Application
Regulates temperature of air or liquids in ducts, pipes, tanks and boilers
Dimensions (in.)
5 5/8 in. high x 2 in. wide x 2 5/8 in. deep
Dimensions (mm)
143 mm high x 51 mm wide x 67 mm deep
Includes
107324A Duct Bulb holder
Comments
Includes 107324A Duct Bulb Holder
Item Type
Product
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
UL Listed: E4436, Vol. 4, Sec. 11, Guide XAPX
Approvals, CSA
CSA Listed: Report -1
Tradeline Value
Tradeline
Contact Ratings
120 Vac-- 8.0 AFL, 48.0 ALR; 240 Vac-- 5.1 AFL, 30.6 ALR; 277 Vac--4.2 AFL, 25.2 ALR
Voltage
120 Vac or 240/277 Vac
Setpoint Temperature Range (C)
71 C to 127 C
Setpoint Temperature Range (F)
160 F to 260 F
Operating Temperature Range (F)
280 F Maximum
Operating Temperature Range (C)
138 C Maximum
Type
Remote bulb
Output
relay
Relay Outputs
1 SPDT
Sensor Inputs
1
Sensor Element
Copper bulb
Capillary Length (ft)
5 ft
Capillary Length (m)
1.5 m
Bulb Size (in.)
1/2 in. x 4 3/16 in.
Bulb Size (mm)
13 mm dia. x 106 mm long
Differential Temperature (F)
3 F to 10 F
Differential Temperature (C)
1.7 C to 5.6 C

Attributes/Specifications

Category Commercial Building Controls
Manufacturer Approved Supplier
Product Standalone Controllers
Style Standalone Controllers

Supplemental Files