The UVT E10 ACW 125-800 is a reliable undervoltage release designed for effective protection in electrical systems. With a voltage rating of 125V, this model ensures safety and efficiency in power management. Made from durable materials, it complies with industry standards for performance and reliability. The compact design allows for easy installation in standard electrical panels, making it compatible with a variety of systems. Ideal for industrial and commercial applications, the UVT E10 ACW 125-800 is essential for safeguarding electrical circuits against undervoltage conditions.

Item # UVT E10 ACW 125-800, Molded Case Circuit Breakers, Accessories, Internal, Under Voltage Release On WEG Electric Corp.

WEG Electric Corp.  :  Controls  :  Molded Case Circuit Breakers, ACW Series  :  Accessories for Molded Case Circuit Breakers  :  Internal Accessories for Molded Case Circuit Breakers  :  Under Voltage Release  :  Item # UVT E10 ACW 125-800

The under voltage release automatically opens a circuit breaker when voltage drops to a value ranging between 35% to 70% of the line voltage. The operation is instantaneous, and after tripping, the circuit breaker cannot be reset until the voltage returns to 85% of line voltage. Range of voltage trip: 0.35?0.7xUn MCCB reset voltage: 0.85xUn (exceed) Frequency: 45?65Hz

Voltage110 to 130VAC/DC
FeaturesThe under voltage release automatically opens a circuit breaker when voltage drops to a value ranging between 35% to 70% of the line voltage. The operation is instantaneous, and after tripping, the circuit breaker cannot be reset until the voltage returns to 85% of line voltage. Range of voltage trip: 0.35…0.7xUn MCCB reset voltage: 0.85xUn (exceed) Frequency: 45…65Hz
For Use With Model NumberACW125...800
Approx. Shipping Weight0.19180194 lbs
DisclaimerData subject to change without notice.

Attributes/Specifications

Manufacturer WEG ELECTRIC CORP
Voltage 110 to 130VAC/DC