This 120VAC Single Stage Standard Opening Intermittent unit is designed for reliable performance in various applications. It features a robust construction that meets industry standards for safety and efficiency. The single-stage design ensures straightforward operation, making it suitable for both residential and commercial use. With its compact size, it can be easily integrated into existing systems. This unit is ideal for those seeking a dependable solution for their HVAC needs, providing consistent performance and energy efficiency.
Residential Comfort/Combustion : Combustion Controls : Gas Valves, Residential : Intermittent Pilot : VR4304 : VR4304M4519/U
Single-stage, 120Vac, Standard Opening, Intermittent Pilot Gas Valve. 3/4 x 3/4". Set 3.5" WC
Overview
Combination gas control for use in 120 Vac, gas-fired, intermittent pilot appliances with capacities from 30 to 415 cfh.
Features
- Controls include safety shutoff, manual valve, two automatic operators, pressure regulator and pilot adjustment.
- Use with S86F,H; S860D; S8600F,H; S8610 and S90A,B Control Modules.
- Compact size. Provide two automatic valves.
- Solenoid operated first automatic valve opens on thermostat call for heat; closes when call for heat ends.
- Diaphragm-operated second automatic valve opens under control of regulator; closes if gas or power supply is interrupted.
- Meet codes requiring dual safety shutoff.
- Standard and slow opening natural gas models include natural to LP gas conversion kit; LP to natural gas conversion kit also available.
- All adjustments, wiring connections and pilot outlet are accessible from top of control.
- Adjustable servo regulator effectively maintains almost constant gas output pressure under wide fluctuations in gas supply pressure.
- Compatible with ECO connector.
- ON-OFF lighting sequence.
Product Specifications
- Application
- Single Stage
- Dimensions (in.)
- 5 3/8 in. high x 4 1/16 in. wide x 2 11/16 in. deep
- Dimensions (mm)
- 135 mm high x 104 mm wide x 69 mm deep
- Includes
- Two 3/4 x 1/2 in. reducer bushings; Natural to LP Conversion Kit; One 1/2" x 3/8" reducer bushing
- Item Type
- Product
- Mounting
- 0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
- Frequency
- 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Component Recognized MCCZ2.MH5323
- Approvals, CSA
- CSA International: 112395
- Tradeline Value
-
- Electrical Connections
- 1/4 in. quick-connect male terminals
- Voltage
- 120 Vac
- Operating Temperature Range (F)
- -40 F to +175 F
- Operating Temperature Range (C)
- -40 C to +79 C
- Body Pattern
- Straight-through
- Opening Characteristics
- Standard
- Pressure Ratings (psi)
- 1/2 psi
- Pressure Ratings (kPa)
- 3.5 kPa
- Inlet/Outlet Size (in.)
- 3/4 in. x 3/4 in.
- Pilot Gas Outlet
- Compression fitting for 1/4 in. OD tubing
- Pressure Tapping
- 1/8 in. NPT with plug
- Approvals, American Gas Association
-
- Type of Fuel
- Natural (LP with included conversion kit)
- Capacity (kBtuh)
- At 1 in. wc p.d.-- 300,000 BTUh: 30,000 BTUh minimum: 415,000 BTUh maximum Natural Gas
- Approvals, Australian Gas Association
- 4717
- Pressure Regulator
- Standard
- Pressure Regulator Setpoint (in. wc)
- 3.5 in. wc
- Pressure Regulator Setpoint (kPa)
- 0.87 kPa
- Ignition Type
- Intermittent Pilot
- Anticipator Setting
-