The Honeywell 10HP NXS Variable Frequency Drive (Model NXBL0100CS10200000) is designed for optimal motor control and energy efficiency. This VFD features advanced CoolBlue bypass technology, allowing for seamless operation and reduced energy consumption. With a power rating of 10HP, it is suitable for a variety of applications, including pumps and fans. The compact design ensures easy installation in tight spaces, while the robust construction meets industry standards for reliability. Ideal for commercial and industrial use, this VFD enhances system performance and longevity.
Commercial Building Controls : Variable Frequency Drives : General Purpose Drives : NXS Drive with Cool Blue Bypass : NXBL0100CS10200000
10HP NXS VFD & 2 CONT. COOLBLUE BYPASS
Overview
Variable Frequency Drives (VFD) accept a control input and then output tailored PWM control signal to operate (motors, fans, pumps, etc.) with maximum efficiency. The VFD can be field-programmed without any extra devices or computer connections.
Features
- Seven configurable applications built in.
- Easy commissioning through software or control panel.
- Devices can be wall-mounted or panel-mounted.
- Eleven protective functions (see Form 63-2600, Users Manual, Technical Data sections).
- Insulated gate bi-polar transistor (IGBT) technology.
- Modbus, BacNet, Device Net, Profibus, LobBus, NS available as options cards.
Product Specifications
- Dimensions (in.)
- 11 x 46 x 10.5
- Dimensions (mm)
- 275 x 1150 x 262.5
- Weight (lb)
- 62 lb
- Weight (kg)
- 28.1 kg
- Item Type
- Product
- Frequency
- 0 Hz to 320 Hz
- Voltage
- 575 Vac
- Operating Temperature Range (F)
- High Overload 14 to 122; Low Overload 14 to 104
- Operating Temperature Range (C)
- High Overload -10 to 50; Low Overload -10 to 40
- Enclosure
- NEMA 1
- Relay Outputs
- 24 Vdc/8A; 125 Vdc/0.4A; 250 Vac/8A
- Horsepower
- 10 HP
- Current Ratings
- 13.5A
- Analog Current Output
- 0 (4) - 20 mA, max 500 ohm
- Bypass
- Drive with 2 contactor bypass
- Auto Bypass
- No
- Drive Family
- NXS
- Contactor
- 2 Contactors
- Disconnect Type
- No Disconnect
- Pilot Lights
- No
- Control Transformer
- No
- Drive Input Disconnect
- No
- Drive Input Fuses
- No
- Type of RFI Filter
- Industrial filter
- Continuous Output Current
- overload 1.5 x High overload current (1min/10min); overload 1.1 x Low overload current (1min/10min)
- Starting Torque
- 200% High; 150% Low
- Peak Current
- 2 x high overload current, 2 seconds every 20 seconds
- Acceleration time
- 0 - 3000 sec
- Deceleration time
- 0 - 3000 sec
- Analog Voltage Input
- 0 - 10 Vdc , 200K ohm
- Analog Current Input
- 0 (4) - 20 mA, 250 ohm differential
- Digital Output
- 50 mA/48v open collector
- Reference Output Voltage
- +10V, +3%, max 10mA
- Auxiliary Voltage
- 24V, 15%, max 250 mA
- Frame Type
- FR5
- Layout
- Vertical