Description
O-Z/Gedney Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof, Series: EYAX, 1/2 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Malleable Iron, Zinc Electroplated, 3-11/16 in L x 1-1/4 in W
Features:
- Smooth, rounded integral bushing in each hub to protect conductor insulation
- Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity
- Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
- Allow up to 40% conduit fill in compliance with the National Electrical Code
- Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
- Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
- Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
- Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit
- Seal must be located within 18 in of either enclosure
- Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations
Applications:
For minimize the passage of gases and vapors and prevent the passage of flames from one portion of the electrical system to another through the conduit
Standards/Approval:
- UL 886
- UL File No. E34997
- CSA C22.2 No. 30
- CSA 009795
- NEC Articles 500-503/505
- Military Specification Mil-F-28675, Class I, Div 1, 2, Groups A, B, C, D, Class I, Zone 1, 2, Groups IIA, IIB, IIC, Class II, Div 1, 2, Groups E, F, G, Class II
Warranty:
Limited