The HONEYWELL 150HP NXS VFD AND 2 CONT COOLBLUE BYPASS is a powerful variable frequency drive designed for 150HP applications. Operating at 230V, this VFD offers superior motor control and energy efficiency, making it ideal for large-scale HVAC systems. The two-contactor design enhances reliability, while the bypass feature allows for uninterrupted operation during maintenance. Built to comply with industry standards, it supports various motor types and is suitable for both commercial and industrial applications. Its advanced technology and robust design ensure optimal performance and energy savings.
Commercial Building Controls : Variable Frequency Drives : General Purpose Drives : NXS Drive with Cool Blue Bypass : NXBL1500CS10200000
150HP NXS VFD & 2 CONT. COOLBLUE BYPASS
Overview
Variable Frequency Drives (VFD) accept a control input and then output tailored PWM control signal to operate (motors, fans, pumps, etc.) with maximum efficiency. The VFD can be field-programmed without any extra devices or computer connections.
Features
- Seven configurable applications built in.
- Easy commissioning through software or control panel.
- Devices can be wall-mounted or panel-mounted.
- Eleven protective functions (see Form 63-2600, Users Manual, Technical Data sections).
- Insulated gate bi-polar transistor (IGBT) technology.
- Modbus, BacNet, Device Net, Profibus, LobBus, NS available as options cards.
Product Specifications
- Dimensions (in.)
- 36 x 54 x 16
- Dimensions (mm)
- 900 x 1350 x 400
- Weight (lb)
- 360 lb
- Weight (kg)
- 163.3 kg
- Item Type
- Product
- Frequency
- 0 Hz to 320 Hz
- Voltage
- 575 Vac
- Operating Temperature Range (F)
- High Overload 14 to 122; Low Overload 14 to 104
- Operating Temperature Range (C)
- High Overload -10 to 50; Low Overload -10 to 40
- Enclosure
- NEMA 1
- Relay Outputs
- 24 Vdc/8A; 125 Vdc/0.4A; 250 Vac/8A
- Horsepower
- 150 HP
- Current Ratings
- 144A
- Analog Current Output
- 0 (4) - 20 mA, max 500 ohm
- Bypass
- Drive with 2 contactor bypass
- Auto Bypass
- No
- Drive Family
- NXS
- Contactor
- 2 Contactors
- Disconnect Type
- No Disconnect
- Pilot Lights
- No
- Control Transformer
- No
- Drive Input Disconnect
- No
- Drive Input Fuses
- No
- Type of RFI Filter
- Industrial filter
- Continuous Output Current
- overload 1.5 x High overload current (1min/10min); overload 1.1 x Low overload current (1min/10min)
- Starting Torque
- 200% High; 150% Low
- Peak Current
- 2 x high overload current, 2 seconds every 20 seconds
- Acceleration time
- 0 - 3000 sec
- Deceleration time
- 0 - 3000 sec
- Analog Voltage Input
- 0 - 10 Vdc , 200K ohm
- Analog Current Input
- 0 (4) - 20 mA, 250 ohm differential
- Digital Output
- 50 mA/48v open collector
- Reference Output Voltage
- +10V, +3%, max 10mA
- Auxiliary Voltage
- 24V, 15%, max 250 mA
- Frame Type
- FR8
- Layout
- Side by Side