KSCdirect

Product Data

KSCdirect Part #: CH FDB2060L
Description: FDB 2P 60A TRIP, 600V CLASS, LINE & LOAD
MFG Part #: FDB2060L
UPC: 621037130333
Supplier: Cutler-Hammer
Usually ships 1-2 business days but timing may vary. Please chat with us if you have questions before ordering.
QTY:  
For shipping rates, add item to cart.
* Quantity discounts may be available. Call Kelly Supply at 800-918-8939.
Alternatively, you may e-mail info@kscdirect.com for service.

Details

Description

Cutler-Hammer Molded Case Circuit Breaker, Type FDB, Series: C Series, 600 V AC/250 V DC, 60 A, 50/60 Hz Frequency, 18 kA at 2410 VAC/14 kA at 480 VAC/14 kA at 600 VAC/10 kA at 250 VDC Interrupt, F Frame, Thermal Magnetic Trip, 2 Pole, 1 ph, Line/Load Connection, NEMA AB1-1993 Enclosure, Surface Mounting, 40 deg C, 6 in H x 2.75 in W x 3.38 in D Dimensions

Features:

  • Patented contact design features high speed blow open action, resulting in superior performance
  • Circuit breakers significantly outperform the calculations listed in The Institute of Electrical and Electronic Engineers (IEEE) standard 1584-2002, guide for performing arc flash hazard calculations

Applications:

Panelboard, Switchboard, Motor Control Center and Busway Applications

Standards/Approval:

  • UL 489
  • CSA C22.2 No. 5
  • HACR Rated
  • RoHS Compliant
  • ARRA Compliant
  • Buy American Act Compliant

Attributes/Specifications

Amperage Rating 60 A
Connection Type Line/Load
Dimensions 6 in H x 2.75 in W x 3.38 in D
Enclosure Type NEMA AB1-1993
Frame F
Frequency Rating 50/60 Hz
Interrupt Rating 18 kA at 2410 VAC/14 kA at 480 VAC/14 kA at 600 VAC/10 kA at 250 VDC
Mounting Type Surface
Number of Poles 2
Phase 1
Series C Series
Temperature Rating 40 deg C
Trip Type Thermal Magnetic
Type Type FDB
Voltage Rating 600 V AC/250 V DC
Manufacturer Cutler-Hammer