The METROPAC L4006B1155 Reverse Acting Aquastat is designed for precise temperature control, operating within a range of 100-240°F with an adjustable differential of 5-30°F. This device is essential for maintaining optimal heating conditions in various applications. Constructed with durable materials, it ensures reliability and longevity. The aquastat features easy installation and compatibility with standard heating systems, making it a versatile choice for HVAC professionals. Its robust design meets industry standards, ensuring compliance and safety in operation.
Residential Comfort/Combustion : Combustion Controls : Aquastats : Aquastats - Single Function : L4006 : L4006B1155/U
Circulator Aquastat controller with 100 f to 240 F operating temperature
Overview
Aquastat Controllers are immersion type devices for limiting or regulating the temperature of liquids in boilers, storage tanks, and other applications where temperature control is required. Honeywell's L4006 are used in applications that utilize the existing wells
Features
- Totally enclosed Micro Switch snap-acting switches operate on temperature rise to setpoint.
- Visible control point scale and external adjustment screw permit easy setting.
- Horizontal or vertical insertion of the sensing element.
- Direct or well immersion of the sensing element.
- Models available for strap-on mounting.
- Remote bulb model may be used to sense air temperature in ducts and in outside air sensing applications.
- TRADELINE models include heat-conductive compound.
- Select models have wells.
- UL limit rated device.
Product Specifications
- Hazmat Information
- UN1294 Toluene
- Application
- Circulator
- Dimensions (in.)
- Case--5 5/8 in. high x 2 in. wide x 2 1/8 in. deep
- Dimensions (mm)
- Case--143 mm high x 51 mm wide x 54 mm deep
- Temperature Range (F)
- Maximum--150 F
- Temperature Range (C)
- Maximum--66 C
- Includes
- Stop factory-set at 240 F (116 C); Heat-conductive compound
- Mounting
- Horizontal or Vertical
- Electrical Ratings
- Millivolt--0.25 A @ 0.25 to 12 Vdc; At Full Load-- 8A @ 120 Vac: 5.1A @ 240 Vac; At Locked Rotor-- 48A @ 120 Vac: 30.6A @ 240 Vac
- Approvals, Underwriters Laboratories Inc.
- UL Component Recognized: File No. MP466, Vol. 6, Sec.1, Guide No. MBPR2
- Approvals, CSA
- Certified: File No. LR95329-1
- Tradeline Value
- Tradeline
- Operating Temperature Range (F)
- 100 F to 240 F
- Operating Temperature Range (C)
- 38 C to 116 C
- Bulb Size (in.)
- 3/8 in. x 2 7/8 in. copper
- Bulb Size (mm)
- 10 mm x 73 mm copper
- Differential Temperature (F)
- 5 F to 30 F adj.
- Differential Temperature (C)
- 3 C to 17 C adj.
- Switching Action
- SPST, contacts make on temperature rise.
- Approvals, American Gas Association
- AGA Certified
- Capillary Length (in.)
- 3 in.
- Capillary Length (mm)
- 76 mm