The NEUCO INC TP972A2242/U Tradeline features a stylish satin chrome cover, designed to enhance the aesthetic of HVAC controls. This cover is not only visually appealing but also durable, ensuring long-lasting performance. It is designed for easy installation and compatibility with standard control systems. The satin chrome finish provides resistance to wear and corrosion, making it suitable for various environments. Ideal for both residential and commercial applications, this cover adds a touch of elegance while maintaining functionality.
Commercial Building Controls : Pneumatic Products : Pneumatic Thermostats : TP972 : TP972A2242/U
Pneumatic Thermostat Direct Acting Cooling, Reverse Acting Heating
Overview
Two-pipe, one- or two-temperature, pneumatic thermostat gives proportional control of pneumatic valves & damper actuators. Replacement kits available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell two-pipe pneumatic thermostats.
Features
- Durable TP970 Series Thermostat. Pilot operated for high capacity.
- Two-temperature energy conservation model available.
- Adapter plate in Convertastat kits covers existing thermostat wall mark.
- Backplate has molded air connections-no separate fittings needed.
- Universal locking cover with satin chrome finish and horizontal, vertical, or blank window options with Tradeline model-other covers available.
Product Specifications
- Application
- Wall Thermostat, Heat/Cool Operation
- Airflow Usage
- 0.011 scfm (5.2 mL/s)
- Dimensions (in.)
- 3 1/4 in. high x 2 in. wide x 1 5/8 in. deep
- Dimensions (mm)
- 83 mm high x 51 mm wide x 41 mm deep
- Maximum Safe Operating Pressure (psi)
- 25 psi
- Maximum Safe Operating Pressure (kPa)
- 170 kPa
- Temperature Range (F)
- 100 F maximum
- Includes
- Thermostat and satin chrome cover.
- Comments
- Tradeline Kit
- Mounting
- Wall mount
- Approvals, Underwriters Laboratories Inc.
-
- Approvals, CSA
-
- Setpoint Temperature Range (F)
- 59 F to 90 F
- Shipping and Storage Temperature Range (F)
- 150 F maximum
- Shipping and Storage Temperature Range (C)
- 66 C maximum
- Approvals, Factory Mutual
-
- Sensor Element
- Bimetal
- Throttling Range (F)
- 2 F to 10 F
- Throttling Range (C)
- 1 C to 5 C
- Connection Size (in.)
-
- Differential Pressure Range (psi)
-
- Differential Pressure Range (kPa)
-
- Approvals, NEMA Standard
-
- Action
- Direct Acting Heating, Reverse Acting Cooling
- Setpoint
- Single
- Number of Pipes
- 2
- Changeover Pressure (psi)
- Heat 18 psi, Cool 13 psi
- Changeover Pressure (kPa)
- Heat 124 kPa, Cool 90 kPa
- Mainline Pressure Range (psi)
-
- Capacity
-
- Control Range (fpm)
-
- Control Range (m/s)
-
- Number of Sensor Inputs
-
- Remote Control Point Adjustment
-
- Approximate Throttling Range, Midscale (psi)
-
- Approximate Throttling Range, Midscale (kPa)
-