The Thermostat from NEUCO INC is designed for precise temperature control in HVAC systems. This device features a user-friendly interface and is compatible with various heating and cooling systems. Constructed with high-quality materials, it ensures reliability and longevity. Its compact design allows for easy installation in residential and commercial settings. Meeting industry standards for performance and safety, this thermostat is essential for maintaining optimal indoor climate conditions.
Commercial Building Controls : Pneumatic Products : Pneumatic Thermostats : TP971 : TP971A2052/U
Pneumatic Thermostat Direct Acting Heating
Overview
Pneumatic thermostat with night setback used for proportional control of pneumatic valves and damper actuators. Replacement kits are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell two-pipe pneumatic thermostats.
Features
- Durable TP970 series thermostat Pilot operated for high capacity.
- Direct Acting (DA) and Reverse Acting (RA) models are available.
- Three-pipe thermostats are available for unit ventilator applications where the outdoor damper must operate when the thermostat is manually set to day operation.
- Adapter plate in thermostat kits covers existing thermostat watermark.
- Backplate has molded air connections-no separate fittings needed.
- Universal Locking cover with satin chrome finish and horizontal, vertical, or blank window options-other covers available.
Product Specifications
- Application
- Wall Thermostat, Day/Night operation
- Airflow Usage
- 0.011 scfm (5.2 mL/s)
- Dimensions (in.)
- 3 1/4 in. high x 2 in. wide x 1 5/8 in. deep
- Dimensions (mm)
- 83 mm high x 51 mm wide x 41 mm deep
- Maximum Safe Operating Pressure (psi)
- 25 psi
- Maximum Safe Operating Pressure (kPa)
- 170 kPa
- Temperature Range (C)
- 38 C maximum
- Includes
- Order Cover Separately
- Mounting
- Wall mount
- Approvals, Underwriters Laboratories Inc.
-
- Approvals, CSA
-
- Setpoint Temperature Range (C)
- Day: 15 C to 30 C, Night: 10 C to 27 C
- Shipping and Storage Temperature Range (F)
- 150 F maximum
- Shipping and Storage Temperature Range (C)
- 66 C maximum
- Approvals, Factory Mutual
-
- Sensor Element
- Bimetal
- Throttling Range (F)
- 2 F to 10 F
- Throttling Range (C)
- 1 C to 5 C
- Connection Size (in.)
-
- Differential Pressure Range (psi)
-
- Differential Pressure Range (kPa)
-
- Approvals, NEMA Standard
-
- Action
- Direct Acting Heating, two temp.
- Setpoint
- Day/Night
- Number of Pipes
- 2
- Changeover Pressure (psi)
- Day 16 psi, Night 21 psi
- Changeover Pressure (kPa)
- Day 110 kPa, 144 kPa
- Mainline Pressure Range (psi)
-
- Capacity
-
- Control Range (fpm)
-
- Control Range (m/s)
-
- Number of Sensor Inputs
-
- Remote Control Point Adjustment
-
- Approximate Throttling Range, Midscale (psi)
-
- Approximate Throttling Range, Midscale (kPa)
-