The Honeywell T678E1003 Temperature Controller offers a temperature range of 40-180°F, making it suitable for a variety of heating and cooling applications. This controller features a maximum element temperature of 20°F, ensuring safe operation in diverse environments. Its user-friendly interface allows for easy adjustments and monitoring, while its compact design facilitates installation in tight spaces. Ideal for HVAC systems, this temperature controller ensures precise temperature regulation, enhancing system efficiency and comfort.
Commercial Building Controls : Standalone Controllers : Temperature Controllers : T678 : T678E1003/U
Remote Temp Control, 40F-180F Range, 2 SPDT, Copper Bulb, 17 ft. Capillary, Switch: 2F Fixed/Interstage: 7F Diff.
Overview
Remote bulb thermostats regulate temperature of air or liquids in ducts, pipes, tanks and boilers.
Features
- Suitable for applications requiring temperature control of air or liquids where controller must be placed outside the sensing area.
- Typical uses include control of dampers and valves in heating, cooling and heating-cooling systems.
- Fast response models (available for use in return air duct) operate approximately four times faster than standard models.
- Controller can be mounted in any position. Ambient temperature compensation provides good temperature control.
- Refer to T775 Electronic Remote Temperature Controller where more exact control is required and/or remote controller location is preferred.
- T678 models have a maximum connected load of 2000 VA.
Product Specifications
- Hazmat Information
- UN1294 Toluene
- Application
- Changeover temperature control
- Dimensions (in.)
- 5 5/8 in. high x 2 in. wide x 2 5/8 in. deep
- Dimensions (mm)
- 143 mm high x 51 mm wide x 67 mm deep
- Comments
- Does not include enclosure
- Item Type
- Product
- Frequency
- 50 Hz; 60 Hz
- Contact Ratings
- 120 Vac-- Control: 2.6 AFL, 15.6 ALR; Hi Limit: 7.4 AFL, 44.4 ALR; 240 Vac-- Control: 1.3 AFL, 7.8 ALR; Hi Limit: 5.1 AFL, 30.6 ALR
- Voltage
- 120 Vac; 240 Vac
- Setpoint Temperature Range (C)
- 4 C to 82 C
- Setpoint Temperature Range (F)
- 40 F to 180 F
- Operating Temperature Range (F)
- 210 F Maximum
- Operating Temperature Range (C)
- 99 C Maximum
- Type
- Remote bulb
- Output
- relay
- Relay Outputs
- 2 SPDT switch contacts
- Sensor Inputs
- 1
- Sensor Element
- Copper bulb
- Capillary Length (ft)
- 17 ft
- Capillary Length (m)
- 5.2 m
- Bulb Size (in.)
- 1/8 in. x 42 in.
- Bulb Size (mm)
- 3 mm x 1064 m
- Differential Temperature (F)
- 2 F
- Differential Temperature (C)
- 1.1 C
- Interstage Differential Temperature (C)
- 3.9 C
- Interstage Differential Temperature (F)
- 7 F