The Cad Cell Relay with a 15-second lockout feature is designed for reliable operation in heating systems. This relay is constructed from high-quality materials, ensuring durability and performance. The LED indicator provides clear status feedback, enhancing usability. Ideal for both residential and commercial applications, this cad cell relay meets industry standards for safety and efficiency, ensuring reliable operation in various heating systems.


Residential Comfort/Combustion : Combustion Controls : Oil Burner Controls : Oil Primaries : R8184G : R8184G4066/U

Protectorelay Oil Burner Control with 15 second safety timing, alarm outputs, and manual safety switch

Overview

Provides automatic, nonrecycling control of an intermittent ignition oil burner system.

Features

  • Controls oil burner, oil valve (if desired) and the ignition transformer in response to a call for heat.
  • Solid state flame sensing circuit.
  • LED on terminal strip indicates system lockout (available on some models).
  • Remote lockout indication (available on some models).
  • Enclosed safety switch with external reset button.
  • Manual trip lever opens safety switch for system maintenance.
  • Mounts on standard 4 x 4 in. junction box; select models may be mounted directly on burner housing.
  • C554A Cadmium Sulfide Flame Detector and 24 Vac thermostat required..

Product Specifications

Dimensions (in.)
4 3/8 in. high x 4 1/8 in. wide x 2 1/2 in. deep
Dimensions (mm)
111 mm high x 104 mm wide x 64 mm deep
Temperature Range (F)
-40 F to +130 F
Temperature Range (C)
-40 C to +54 C
Comments
With LED for lockout indication, and manual trip lever on safety switch to assure burner shutdown during servicing.
Item Type
Product
Mounting
For mounting on a standard 4 in. X 4 in. junction box or direct mounting on burner housing.
Approvals, Underwriters Laboratories Inc.
UL Component Recognized; File no. MP268, Vol. 35 Sec. 1,3
Approvals, CSA
CSA Certified; File no. LR95329-1
Tradeline Value
Tradeline
Ignition Type
Intermittent
Timing, Safety Switch
15 sec.
Electrical Ratings, Contacts (full load)
7.4 A @ 120 Vac; 3.7 a @ 240 Vac
Electrical Ratings, Contacts (locked rotor)
44.4 A @ 120 Vac; 22.2 A @ 240 Vac
Alarm Load Ratings (pilot duty)
75 VA @ 120/240 Vac, 50-60 Hz; 25 VA @ 24V, 50-60 Hz
Alarm Load Ratings (resistive)
1.5 A @ 120/240V, 50-60Hz; 3 A @ 24 V, 50-60 Hz