The Color Coded Intr from NEUCO INC is an essential component for organizing and identifying wiring in complex systems. This product features a vibrant color coding system that enhances visibility and simplifies installation. Made from durable materials, it ensures long-lasting performance in various environments. Ideal for use in electrical panels, control systems, and other applications, this product helps maintain order and efficiency in wiring setups. Its design complies with industry standards, making it a reliable choice for professionals.
Commercial Building Controls : Pneumatic Products : Pneumatic Thermostats : LP916 : LP916B1090/U
Pneumatic Remote Bulb Thermostat Direct Heating, Reverse Cooling Acting
Overview
Two-pipe, single temperature, unit mounted, remote bulb pneumatic thermostat used to provide proportional control of pneumatic valves and damper actuators in heating and air conditioning systems.
Features
- Liquid filled remote bulb.
- Direct Acting (DA), Reverse Acting (RA) and Heating/Cooling (DA/RA) models are available.
Product Specifications
- Application
-
- Airflow Usage
- 0.011 scfm (5.2 mL/s) with 0.005 in. restriction
- Dimensions (in.)
- 4 3/4 in. high x 3 3/4 in. wide x 3 in. deep
- Dimensions (mm)
- 121 mm high x 95 mm wide x 76 mm deep
- Maximum Safe Operating Pressure (psi)
- 25 psi
- Maximum Safe Operating Pressure (kPa)
- 170 kPa
- Temperature Range (F)
- 135 F maximum
- Temperature Range (C)
- 57 C maximum
- Includes
- Integral Mounting Bracket, (2) 316297-00021 Bulb Hangers and 304528A Bag Assembly (mounting hardware).
- Mounting
- In compartment of a unit ventilator
- Approvals, Underwriters Laboratories Inc.
-
- Approvals, CSA
-
- Setpoint Temperature Range (C)
- 19 C to 30 C
- Setpoint Temperature Range (F)
- 65 F to 85 F
- Shipping and Storage Temperature Range (F)
- 150 F maximum
- Shipping and Storage Temperature Range (C)
- 66 C maximum
- Approvals, Factory Mutual
-
- Sensor Element
- Bulb 3/8 x 9 in., capillary 36 in. (914 mm) long; Remote Bulb
- Throttling Range (F)
- 3.5 F
- Throttling Range (C)
- 2 C
- Connection Size (in.)
-
- Differential Pressure Range (psi)
-
- Differential Pressure Range (kPa)
-
- Approvals, NEMA Standard
-
- Action
- Direct Acting Heating, Reverse Acting Cooling
- Air connections
- Barb fittings 1/4 in. (6 mm)
- Setpoint
- Single
- Number of Pipes
- 2
- Scale Markings
- Warmer / Cooler
- Changeover Pressure (psi)
- Heat 18 psi, Cool 13 psi
- Changeover Pressure (kPa)
- Heat 124 kPa, Cool 90 kPa
- Mainline Pressure Range (psi)
-
- Capacity
-
- Control Range (fpm)
-
- Control Range (m/s)
-
- Number of Sensor Inputs
-
- Remote Control Point Adjustment
-
- Approximate Throttling Range, Midscale (psi)
-
- Approximate Throttling Range, Midscale (kPa)
-