The Remote Bulb Aquastat from METROPAC operates within a temperature range of 100-240°F and features a 5-1/2' capillary tube for flexible installation. This device is essential for maintaining optimal temperature control in heating systems. Its robust design ensures reliable performance and compliance with industry standards. The aquastat is compatible with various heating applications, making it a versatile choice for HVAC professionals seeking efficiency and reliability.
Residential Comfort/Combustion : Combustion Controls : Aquastats : Aquastats - Single Function : L6008 : L6008A1192/U
Low limit controller with 66 inch capillary, SPDT, operating range 100 - 240F, factory stop at 240F
Overview
Aquastat Controllers are immersion type devices for limiting or regulating the temperature of liquids in boilers, storage tanks, and other applications where temperature control is required.
Features
- Remote temperature sensing element detects and responds rapidly to temperature changes.
- Totally enclosed Micro Switch snap-acting switch.
- Visible control point scale and external adjustment screw permit easy setting.
- Available horizontal or vertical mounting of the remote element into boiler, tank, or other container.
- Case mounts to a vertical surface.
Product Specifications
- Hazmat Information
- UN1294 Toluene
- Application
- Circulator Control and Low Limit
- Dimensions (in.)
- Case--5 5/8 in. high x 2 in. wide x 2 1/8 in. deep
- Dimensions (mm)
- Case--143 mm high x 51 mm wide x 54 mm deep
- Temperature Range (F)
- Maximum Ambient--150 F
- Temperature Range (C)
- Maximum Ambient--66 C
- Includes
- 66 in. capillary; Stop factory-set at 240 F (116 C)
- Mounting
- Horizontal or Vertical
- Electrical Ratings
- Millivolt--0.25 A @ 0.25 to 12 Vdc; At Full Load-- 8A @ 120 Vac: 5.1A @ 240 Vac; At Locked Rotor-- 48A @ 120 Vac: 30.6A @ 240 Vac
- Approvals, Underwriters Laboratories Inc.
- UL Component Recognized: File No. MP466, Vol. 6, Sec.1, Guide No. MBPR2
- Approvals, CSA
- Certified: File No. LR95329-1
- Operating Temperature Range (F)
- 100 F to 240 F
- Operating Temperature Range (C)
- 38 C to 116 C
- Bulb Size (in.)
- 3/8 in. x 2 7/8 in. copper
- Bulb Size (mm)
- 10 mm x 73 mm copper
- Differential Temperature (F)
- 5 F to 30 F adj.
- Differential Temperature (C)
- 3 C to 17 C adj.
- Switching Action
- SPDT