KSCdirect

Product Data

KSCdirect Part #: HON L4081B1096/U
Description: Dual Aquastat 130-240F 10 Fixed Differential
MFG Part #: L4081B1096
UPC: 85267053440
Supplier: Approved Supplier
Usually ships in 1-2 days.
You will be notified of any delay and may cancel at that time.

Your Price: $377.29 / EA

QTY:  
For shipping rates, add item to cart.
* Quantity discounts may be available. Call Kelly Supply at 800-918-8939.
Alternatively, you may e-mail info@kscdirect.com for service.

Details

The METROPAC Dual Aquastat operates within a temperature range of 130-240°F, featuring a fixed differential of 10°F. This device is essential for maintaining optimal heating conditions in various systems. Its robust design ensures compliance with industry standards, providing reliable performance in demanding environments. The aquastat is compatible with a wide range of heating applications, making it a versatile choice for HVAC professionals. Its easy installation and precise temperature control capabilities enhance system efficiency.


Residential Comfort/Combustion : Combustion Controls : Aquastats : Aquastats Oil - Multifunction : L4081 : L4081B1096/U

High/Low Limit Circulator Aquastat Controller, 10F degree fixed differential, 3 in insulation depth

Overview

High limit, low limit and/or circulator controllers used to regulate boiler water temperature in gas- or oil-fired hydronic heating systems.

Features

  • An immersion type liquid-filled sensing element actuates two snap switches.
  • One switch operates as a high limit control.
  • The other switch operates as a low limit and/or circulator control, depending on the model.
  • Controller may be mounted in any positioning and needs no leveling.
  • Separate, easy-to-read, calibrated dial and setpoint adjustments for each switch.
  • Differential adjustment on low limit or circulator switch on select models.
  • All adjustments accessible inside front cover.
  • Push-in terminals for quick connecting.
  • Single sensing element for easy installation.
  • Two SPST snap switches act independently at respective temperature settings..

Product Specifications

Hazmat Information
UN1294 Toluene
Application
High Limit and Circulator
Dimensions (in.)
3 7/8 in. high x 4 1/8 in. wide x 2 3/4 in. deep.
Dimensions (mm)
98 mm high x 105 mm wide x 70 mm deep.
Temperature Range (F)
Maximum--150 F at switches; 265 F at sensing element
Temperature Range (C)
Maximum--66 C at switches; 129 C at sensing element
Mounting
Horizontal
Electrical Ratings
0.25 A @ 0.25 to 12 Vdc; At Full Load-- 8A @ 120 Vac: 5.1A @ 240 Vac; At Locked Rotor-- 48A @ 120 Vac: 30.6A @ 240 Vac
Approvals, Underwriters Laboratories Inc.
UL Listed: File No. MP466, Vol. 12, Sec. 4, Guide No. MBPR2
Approvals, CSA
Certified: File No. LR95329-1
Operating Humidity Range (% RH)
0 to 95% RH, non-condensing
Operating Temperature Range (F)
High Limit-- 130 F to 240 F; Low Limit-- 110 F to 220 F
Operating Temperature Range (C)
High Limit-- 54 C to 116 C; Low Limit-- 43 C to 104 C
Differential Temperature (F)
10 F Fixed
Switching Action
SPST: High Limit & Circulator
Insulation Depth (in.)
3 in.
Insulation Depth (mm)
76 mm
Electrical Ratings, Ignition
Transformer Load: 360 VA

Attributes/Specifications

Category Residential Comfort/Combustion
Manufacturer Approved Supplier
Product Combustion Controls

Supplemental Files

This item has no supplemental files.