The VFD BYP 230V 75HP N1 3CONT FD by HONEYWELL is engineered for high-performance applications requiring variable frequency drives. Operating at 230V, this 75HP VFD is suitable for three-phase motors, providing precise speed control and energy savings. Its advanced features include multiple control modes and built-in protection mechanisms, ensuring reliable operation in demanding environments. The compact design allows for easy integration into existing systems, while compliance with industry standards guarantees safety and efficiency. Ideal for HVAC and industrial applications, this VFD enhances system performance and reduces operational costs.
Commercial Building Controls : Variable Frequency Drives : SmartVFD HVAC : SmartVFD Bypass : HVFDSB3B0750G130/U
SmartVFD BYPASS, 230VAC, 75 HP,NEMA 1 Enclosure, Three Contactor Bypass
Overview
The SmartVFD BYPASS is available in four configurations to meet your application needs: Disconnect Only, Two Contractor Bypass, Three Contractor Bypass, and Three Contractor with Auto-Bypass.
Features
- Provides an economical means of bypassing the VFD
- Freeze/Fire/Smoke Interlock
- Fused Disconnect on some models
- 3-Contactor bypass provides VFD isolation from power with motor running in BYPASS mode
- 3-Contactor bypass provides TEST position powers the VFD without sending power to the motor
- 3-Contactor Bypass with Auto-Bypass adds the control capabilities below to the standard three Contactor Bypass
Product Specifications
- Dimensions (in.)
- 25 x 70 x 16.2
- Dimensions (mm)
- 635 x 1778 x 411.48
- Weight (lb)
- 331
- Weight (kg)
- 150.14
- Item Type
- Product
- Frequency
- 0 Hz to 320 Hz
- Voltage
- 230 Vac
- Operating Temperature Range (F)
- 14 F to 122 F
- Operating Temperature Range (C)
- -10 C to 50 C
- Enclosure
- NEMA 1
- Relay Outputs
- Max. switching load: 250Vac/2A or 250Vdc/0,4A
- Horsepower
- 75 HP
- Current Ratings
- 205 A
- Analog Current Output
- 0 (4) - 20 mA, max 500 ohm
- Bypass
- Drive with 3 contactor bypass
- Auto Bypass
- No
- Drive Family
- SmartVFD HVAC
- Contactor
- 3 Contactors
- Disconnect Type
- Fused
- Pilot Lights
- Yes
- Drive Input Disconnect
- Yes
- Drive Input Fuses
- Yes
- Type of RFI Filter
- EMC Filter
- Continuous Output Current
- overload 1.5 x High overload current (1min/10min); overload 1.1 x Low overload current (1min/10min)
- Starting Torque
- Depends on the Motor
- Acceleration time
- 0.1 - 3000 sec
- Deceleration time
- .1 - 3000 sec
- Analog Voltage Input
- 0 - 10 Vdc , 200K ohm
- Analog Current Input
- 0 (4) - 20 mA, 250 ohm differential
- Digital Output
- Open collector, max. load 48V/50mA
- Reference Output Voltage
- Maximum Load 10mA
- Auxiliary Voltage
- 20%, max. load 50 mA
- Frame Type
- 8