The HONEYWELL VFD BYPASS 230V 50HP N3R 2CONT is a reliable solution for motor control, designed to operate at 230 volts with a 50 horsepower rating. This variable frequency drive bypass system features a two contact configuration, allowing for flexible operation in various applications. Built to NEMA 3R standards, it provides protection against water and dust, making it suitable for outdoor installations. The compact design ensures easy integration into existing systems, while the seamless transition between VFD and bypass modes enhances energy efficiency and operational reliability.
Commercial Building Controls : Variable Frequency Drives : SmartVFD HVAC : SmartVFD Bypass : HVFDSB3B0500G320/U
SmartVFD BYPASS, 230VAC, 50 HP,NEMA 3R Enclosure, Two Contactor Bypass
Overview
The SmartVFD BYPASS is available in four configurations to meet your application needs: Disconnect Only, Two Contractor Bypass, Three Contractor Bypass, and Three Contractor with Auto-Bypass.
Features
- Provides an economical means of bypassing the VFD
- Freeze/Fire/Smoke Interlock
- Fused Disconnect on some models
- 3-Contactor bypass provides VFD isolation from power with motor running in BYPASS mode
- 3-Contactor bypass provides TEST position powers the VFD without sending power to the motor
- 3-Contactor Bypass with Auto-Bypass adds the control capabilities below to the standard three Contactor Bypass
Product Specifications
- Dimensions (in.)
- 60 x 41 x 14
- Dimensions (mm)
- 1524 x 1041 x 356
- Weight (lb)
- 185
- Weight (kg)
- 83.91
- Item Type
- Product
- Frequency
- 0 Hz to 320 Hz
- Voltage
- 230 Vac
- Operating Temperature Range (F)
- 14 F to 122 F
- Operating Temperature Range (C)
- -10 C to 50 C
- Enclosure
- NEMA 3R
- Relay Outputs
- Max. switching load: 250Vac/2A or 250Vdc/0,4A
- Horsepower
- 50 HP
- Current Ratings
- 140 A
- Analog Current Output
- 0 (4) - 20 mA, max 500 ohm
- Bypass
- Drive with 2 contactor bypass
- Auto Bypass
- No
- Drive Family
- SmartVFD HVAC
- Contactor
- 2 Contactors
- Drive Input Disconnect
- No
- Type of RFI Filter
- EMC Filter
- Continuous Output Current
- overload 1.5 x High overload current (1min/10min); overload 1.1 x Low overload current (1min/10min)
- Starting Torque
- Depends on the Motor
- Acceleration time
- 0.1 - 3000 sec
- Deceleration time
- .1 - 3000 sec
- Analog Voltage Input
- 0 - 10 Vdc , 200K ohm
- Analog Current Input
- 0 (4) - 20 mA, 250 ohm differential
- Digital Output
- Open collector, max. load 48V/50mA
- Reference Output Voltage
- Maximum Load 10mA
- Auxiliary Voltage
- 20%, max. load 50 mA
- Frame Type
- 8