The HONEYWELL SMARTVFD BYPASS operates at 230 VAC and supports a 25 horsepower rating, making it ideal for various motor control applications. This bypass system is designed to provide seamless transition between VFD and bypass modes, ensuring continuous operation. Constructed to meet NEMA 3R standards, it is suitable for outdoor use, providing protection against rain and dust. The compact design allows for easy installation, while the advanced features enhance energy efficiency and system reliability. Perfect for HVAC and industrial applications, this SMARTVFD BYPASS ensures optimal performance and longevity.
Commercial Building Controls : Variable Frequency Drives : SmartVFD HVAC : SmartVFD Bypass : HVFDSB3B0250G331/U
SmartVFD BYPASS, 230 Vac,25 HP, Graphical, NEMA 3R Enclosure, Three Contactor Bypass with Auto Bypass
Overview
The SmartVFD BYPASS is available in four configurations to meet your application needs: Disconnect Only, Two Contractor Bypass, Three Contractor Bypass, and Three Contractor with Auto-Bypass.
Features
- Provides an economical means of bypassing the VFD
- Freeze/Fire/Smoke Interlock
- Fused Disconnect on some models
- 3-Contactor bypass provides VFD isolation from power with motor running in BYPASS mode
- 3-Contactor bypass provides TEST position powers the VFD without sending power to the motor
- 3-Contactor Bypass with Auto-Bypass adds the control capabilities below to the standard three Contactor Bypass
Product Specifications
- Dimensions (in.)
- 28.5 x 48 x 14
- Dimensions (mm)
- 711.2 x 1219.2 x 355.6
- Weight (lb)
- 193
- Weight (kg)
- 87.54
- Item Type
- Product
- Frequency
- 0 Hz to 320 Hz
- Voltage
- 230 Vac
- Operating Temperature Range (F)
- 14 F to 122 F
- Operating Temperature Range (C)
- -10 C to 50 C
- Enclosure
- NEMA 3R
- Relay Outputs
- Max. switching load: 250Vac/2A or 250Vdc/0,4A
- Horsepower
- 25 HP
- Current Ratings
- 75A
- Analog Current Output
- 0 (4) - 20 mA, max 500 ohm
- Bypass
- Drive with 3 contactor bypass and Auto bypass
- Auto Bypass
- Yes
- Drive Family
- SmartVFD HVAC
- Contactor
- 3 Contactors
- Disconnect Type
- Fused
- Pilot Lights
- Yes
- Drive Input Disconnect
- Yes
- Drive Input Fuses
- Yes
- Type of RFI Filter
- EMC Filter
- Continuous Output Current
- overload 1.5 x High overload current (1min/10min); overload 1.1 x Low overload current (1min/10min)
- Peak Current
- 2 x IN, 2 seconds every 20 second period
- Acceleration time
- 0.1 - 3000 sec
- Deceleration time
- .1 - 3000 sec
- Analog Voltage Input
- 0 - 10 Vdc , 200K ohm
- Analog Current Input
- 0 (4) - 20 mA, 250 ohm differential
- Digital Output
- Open collector, max. load 48V/50mA
- Reference Output Voltage
- Maximum Load 10mA
- Auxiliary Voltage
- 20%, max. load 50 mA
- Frame Type
- 6