The HONEYWELL HVFDSB3A0600G310/U is a 60HP VFD bypass designed for 208V applications. This unit features a N3R enclosure, ensuring protection against environmental factors. It is engineered for efficient motor control, providing smooth operation and energy savings. Ideal for industrial applications, it complies with relevant standards for safety and performance. The VFD's robust design allows for reliable operation in demanding conditions, making it a perfect choice for various motor-driven systems.
Commercial Building Controls : Variable Frequency Drives : SmartVFD HVAC : SmartVFD Bypass : HVFDSB3A0600G310/U
SmartVFD BYPASS, 208 Vac, 60 HP,Graphical, NEMA 3R Enclosure, Fused Disconnect Only
Overview
The SmartVFD BYPASS is available in four configurations to meet your application needs: Disconnect Only, Two Contractor Bypass, Three Contractor Bypass, and Three Contractor with Auto-Bypass.
Features
- Provides an economical means of bypassing the VFD
- Freeze/Fire/Smoke Interlock
- Fused Disconnect on some models
- 3-Contactor bypass provides VFD isolation from power with motor running in BYPASS mode
- 3-Contactor bypass provides TEST position powers the VFD without sending power to the motor
- 3-Contactor Bypass with Auto-Bypass adds the control capabilities below to the standard three Contactor Bypass
Product Specifications
- Dimensions (in.)
- 48 x 36 x 16
- Dimensions (mm)
- 1219 x 914 x 406
- Weight (lb)
- 149
- Weight (kg)
- 67.59
- Item Type
- Product
- Frequency
- 0 Hz to 320 Hz
- Voltage
- 208 Vac
- Operating Temperature Range (F)
- 14 F to 122 F
- Operating Temperature Range (C)
- -10 C to 50 C
- Enclosure
- NEMA 3R
- Relay Outputs
- Max. switching load: 250Vac/2A or 250Vdc/0,4A
- Horsepower
- 60 HP
- Current Ratings
- 170 A
- Analog Current Output
- 0 (4) - 20 mA, max 500 ohm
- Bypass
- Drive with Fused Disconnect
- Auto Bypass
- No
- Drive Family
- SmartVFD HVAC
- Disconnect Type
- Fused
- Drive Input Disconnect
- Yes
- Drive Input Fuses
- Yes
- Type of RFI Filter
- EMC Filter
- Continuous Output Current
- overload 1.5 x High overload current (1min/10min); overload 1.1 x Low overload current (1min/10min)
- Starting Torque
- Depends on the Motor
- Acceleration time
- 0.1 - 3000 sec
- Deceleration time
- .1 - 3000 sec
- Analog Voltage Input
- 0 - 10 Vdc , 200K ohm
- Analog Current Input
- 0 (4) - 20 mA, 250 ohm differential
- Digital Output
- Open collector, max. load 48V/50mA
- Reference Output Voltage
- Maximum Load 10mA
- Auxiliary Voltage
- 20%, max. load 50 mA
- Frame Type
- 8