The CO2 Duct Sensor from NEUCO INC is designed for monitoring carbon dioxide levels in HVAC systems. This sensor features a dual output of 2-10VDC and 0-4-20mA, providing flexibility for integration into various control systems. Its compact design allows for easy installation in ductwork, ensuring accurate readings in real-time. The display feature enhances usability, making it easy to monitor CO2 levels. Built to meet industry standards, this sensor is essential for maintaining indoor air quality and optimizing HVAC performance.
Commercial Building Controls : Sensors : CO2 Sensors : C7232 : C7232B1022/U
Duct Mount CO2 Sensor with display,0/2-10Vdc or 0/4-20mA output
Overview
These stand-alone Carbon Dioxide (CO2) Sensors and Controllers are used for determining ventilation necessity with HVAC controllers and to manage the amount of fresh outdoor air supplied to maintain acceptable levels of CO2 in the space.
Features
- Models available with LCD that provides sensor readings and status information.
- Non-Dispersion-Infrared (NDIR) technology used to measure carbon dioxide gas.
- Gold-plated sensor provides long-term calibration stability.
- C7232 provides voltage or current output based on CO2 levels.
- SPST relay output.
- Used for CO2 based ventilation control (Demand Control Ventilation (DCV)).
- Automatic Background Calibration (ABC) algorithm based on long-term evaluation reduces required typical zero-drift check maintenance.
Product Specifications
- Application
- Carbon Dioxide Sensor
- Dimensions (in.)
- 5 5/8 in. high x 3 5/16 in. wide x 3 7/16 in. deep x plus 8 in. long sensing tube
- Dimensions (mm)
- 142 mm high x 84 mm wide x 87 mm deep x plus 203 mm sensing tube
- Includes
- No Honeywell Logo
- Item Type
- Product
- Mounting
- Duct mount
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Listed, File No. E4436
- Electrical Connections
- Six leadwires, 20-gauge, 6 in. long
- Sensor
- Non-dispersive Infrared (NDIR)
- Contact Ratings
- 1 A @ 50 Vac/24 Vdc
- Voltage
- 24 Vac/dc 20%,
- Operating Temperature Range (F)
- 32 F to 122 F
- Operating Temperature Range (C)
- 0 C to 50 C
- Relay Outputs
- One: Normally Open SPST
- Timing
- Response--1 minute
- Accuracy
- 5% full scale
- Display
- Yes
- Sensor Range
- 0 to 2000 ppm, adjustable
- Analog Current Output
- 0/2 - 10 Vdc or 0/4 - 20 mA selectable, w/ one relay output