The 20K DUCT AVERAGING TEMP SENSOR from NEUCO INC is designed for accurate temperature measurement in duct systems. With a 12-foot lead, this sensor is ideal for installation in various HVAC applications. It features a 20K ohm resistance, ensuring precise readings and reliable performance. This sensor is built to withstand harsh environments, making it suitable for both commercial and industrial use. Its compatibility with standard control systems allows for seamless integration, enhancing overall system efficiency and performance.
Commercial Building Controls : Sensors : Temperature Sensors : C7041 : C7041J2007/U
20K ohm NTC Duct Averaging Temp Sensor,12ft, Operating range -40-250F
Overview
The C7041 Electronic Temperature Sensors are 20K ohm NTC sensors designed to be used with electronic controllers in domestic or commercial heating and cooling systems.
Features
- The C7041 series of electronic temperature sensors are designed for use with the Excel 10, Excel 15, or any controller requiring a 20K ohm NTC non-linearized sensor input.
- Various models are available for sensing duct air temperature, averaging air temperature, water temperature, outdoor air temperature, or water pipe temperature.
- All devices consist of a temperature sensitive element and leadwires enclosed for protection from physical damage.
- Sensor element enclosures are made of various lengths and configurations for the specific applications.
- All devices have a wiring box housing to enclose the field wiring connections. C7041F outdoor sensor design, made of aluminum and stainless steel, is waterproof, and includes a sunshield.
Product Specifications
- Application
- Duct air (averaging)
- Dimensions (in.)
- 4 3/16 in. high x 2 5/16 in. wide x 1 11/16 in. deep
- Dimensions (mm)
- 107 mm high x 59 mm wide x 43 mm deep
- Used With
- Excel 10, 50, 80, 100, 500
- Item Type
- Product
- Sensor
- 20 K ohm NTC @ 77 F
- Operating Temperature Range (F)
- -40 F to +250 F
- Operating Temperature Range (C)
- -40 C to +121 C
- Shipping and Storage Temperature Range (F)
- -30 F to +160 F
- Shipping and Storage Temperature Range (C)
- -34 C to +71 C
- Insertion Length (in.)
- 12 ft.
- Insertion Length (mm)
- 3.66 m
- Ambient Temperature Range (F)
- 302 F Maximum
- Ambient Temperature Range (C)
- 150 C Maximum