The Direct Connect Water Heater Kit includes a 3/4" assembly compliant with ASSE 1017 standards, ensuring safe and efficient water heating. This kit is designed for easy installation and compatibility with various water heating systems. Constructed from high-quality materials, it guarantees durability and long-lasting performance. The kit includes all necessary components for a complete setup, making it ideal for both residential and commercial applications. Its reliable design ensures optimal water temperature control and energy efficiency.
Residential Comfort/Combustion : Potable water products : Thermostatic Mixing Valves : AMX300 Series DirectConnect : AMX300TLF/U
DirectConnect water heater kit including valve, tee, and 8 in. flex connector (low lead)
Overview
Honeywell AMX300 series DirectConnect kits reduce installation time while providing Honeywell's industry-leading mixing valve technology, which offers excellent temperature stability and control and minimizes scalding risk to building occupants.
Features
- Temperature is adjustable using push-twist-release locking hand wheel design and if cold water supply is interrupted, flow reduction occurs in seconds
- Kit includes mixing valve, cold water tee fitting and flexible stainless steel connector
- Recirculation portion option offers fast delivery of heated water to the furthest fixtures, increasing user comfort with more available hot water
- The alternate hot port bypasses hot water directly from the tank to non-mixed temperature applications
- Fits most water heaters up to 1 in., with all necessary adapters included
- Brass/stainless construction with Teflon coated wear surfaces for extended surface
- Lead free products have products numbers end in LF
Product Specifications
- Application
- Domestic Hot Water
- Maximum Safe Operating Pressure (psi)
- 150 psi
- Comments
- Low lead Content <.25% by weighted average
- Operating Temperature Range (F)
- 33 F to 80 F (cold water inlet); 100 F to 212 F (hot water inlet)
- Operating Temperature Range (C)
- 0.5 C to 27 C (cold water inlet); 38 C to 100 C) (hot water inlet)
- Minimum flow rate (gpm)
- 0.25 gpm; Recirculation Port: 1/2 in. NPT; Alternate Hot Port: 1/2 in. NPT
- Connection Type
- Hot Inlet - Female NPT; Mixed Outlet - Male NPT
- Pipe Size (inch)
- 1/2 in.
- Pipe Size (DN)
- DN15
- Fluid Temperature (C)
- Mixed Water Supply--38 C to 63 C
- Fluid Temperature (F)
- Mixed Water Supply--100 F to 145 F
- Capacity (Cv)
- 2.3 Cv
- Valve Type
- Mixing Valves
- Minimum flow rate (lpm)
- 0.95 lpm; Recirculation Port: 1/2 in. NPT; Alternate Hot Port: 1/2 in. NPT