KSCdirect

Product Data

KSCdirect Part #: HON W7100C1018/U
Description: STANDARD
MFG Part #: W7100C1018/U
UPC: 85267116534
Supplier: Approved Supplier
Usually ships in 1-2 days.
You will be notified of any delay and may cancel at that time.

Your Price: $4259.61 / EA

QTY:  
For shipping rates, add item to cart.
* Quantity discounts may be available. Call Kelly Supply at 800-918-8939.
Alternatively, you may e-mail info@kscdirect.com for service.

Details

The NEUCO INC W7100C1018/U standard component is designed for versatile applications across various industries. This product features a robust construction, ensuring durability and reliability in demanding environments. Its compact design allows for easy installation and integration into existing systems. Compliant with industry standards, this standard component is suitable for both commercial and industrial use, enhancing overall system performance and efficiency.


Commercial Building Controls : Building Management Systems : Controllers (Legacy) : W7100A,C : W7100C1018/U

20 to 30 Vac Discharge air temp. cntrl.

Overview

Maintain an average discharge air temperature in variable air volume systems. Reduce kilowatt demand & consumption by maintaining the minimum amount of heating or cooling capacity required to hold the discharge air set point.

Features

  • W7100 Controller maintains an average discharge air temperature in variable air volume (VAV) cooling systems by modulating an economizer and sequencing stages of mechanical cooling.
  • The W7100 can be applied to electric makeup air and other systems requiring discharge air control of multistage heating or cooling.
  • Staging capacity of the W7100A,C can be extended six stages using a W7101A Satellite Sequencer.
  • When power is interrupted, the system cycles to all stages off.
  • When power is restored, the economizer will first be modulated open (if enthalpy is suitable), then stages of mechanical cooling will be sequenced on.
  • If enthalpy is not suitable for economizer operation, the first stage of cooling or heating is energized within five minutes.
  • Reset signal from either space sensor or outdoor air sensor.

Product Specifications

Application
Discharge Air
Dimensions (in.)
8 5/8 in. high x 6 1/2 in. wide x 3 in. deep
Dimensions (mm)
219 mm high x 161 mm wide x 76 mm deep
Comments
Additional stages of heating and cooling can be achieved by adding a W7101 Satellite Sequencer
Frequency
50 Hz; 60 Hz
Electrical Connections
1/4 in. quick-connect male terminals
Application Size
2 Heat / 4 Cool
Control System
W7100 family
Output Type
Staged On/Off
Contact Ratings
NO 750 VA inrush @ 120/240 Vac, 75 VA running @ 120/240 Vac; NC 240 VA inrush @ 40 Vac, 30 VA running @ 24 Vac; NO 240 VA inrush @ 24 Vac, 60 VA running @ 24 Vac; NC 75 VA inrush @ 24 Vac, 30 VA running @ 24 Vac
Power Consumption
12 VA at 24 Vac, 50/60 Hz (max).
Voltage
20 to 30 Vac
Setpoint Temperature Range (C)
4 C to 32 C
Setpoint Temperature Range (F)
40 F to 90 F
Operating Temperature Range (F)
40 F to 90 F
Operating Temperature Range (C)
4 C to 32 C
Shipping and Storage Temperature Range (F)
-40 F to +150 F
Shipping and Storage Temperature Range (C)
-40 C to +65 C

Attributes/Specifications

Category Commercial Building Controls
Manufacturer Approved Supplier
Product Building Management Systems
Style Building Management Systems

Supplemental Files