V4044A1001
120V 1/2 in. Flare Connection Line Voltage Motorized Zone Valves with
4 Cv capacity
Locate Distributors
Product Specifications Literature and
Documents
Overview
On-off and diverting line voltage valves consist of an actuator motor
and valve assembly for controlling the flow of hot or chilled water.
Features
o Manual opener (on all models, except straight-through, normally
open valves) for valve operation on power failure; valve returns to
automatic position when power is restored.
o All models may be installed without disassembling the valve.
o Compact construction for easy installation.
o Complete powerhead may be removed or replaced without breaking
plumbing line connections or draining the system.
o Motor may be replaced without removing the valve body or draining
the system.
o Suitable for heating and cooling applications.
Product Specifications Back To Top
Description 120V 1/2 in. Flare Connection Line Voltage Motorized Zone
Valves
Application Hydronic Control
Connection Type Flare
Pipe Size (inch) 1/2 in.
Pipe Size (DN) DN15
Body Pattern 3-Way, Diverting
Capacity (Cv) 4 Cv
Capacity (Kv) 3.4 Kv
De-energized Position Port A Normally Closed
Maximum Close-off Pressure (psi) 20 psi
Maximum Close-off Pressure (kPa) 138 kPa
Fluid Temperature Range (F) 40 F to 200 F
Fluid Temperature Range (C) 5 C to 93 C
Electrical Connections (in.) 18 in. leads
Electrical Connections (mm) 457 mm leads
Power Consumption 9.6 VA
Nominal Timing (sec, min) 30 sec
Valve Action Spring Return to port A
Maximum Ambient Temperature (F) 125 F
Maximum Ambient Temperature (C) 52 C
Dimensions (in.) 5 3/8 in. high x 4 11/16 in. wide x 2 3/8 in. deep
Dimensions (mm) 136 mm high x 118 mm wide x 60 mm deep
Type 2 position
Static Pressure (psi) 125 psi
Static Pressure (kPa) 862 kPa
Materials (Body) Brass
Materials (Seat) Brass
Materials (Stem) Stainless Steel
Materials (Ball Plug) Buna-N (NBR) Rubber Ball
Materials (Packing O-rings) EPDM rubber
Voltage 120 Vac
Frequency 60 Hz
Approvals, Underwriters Laboratories Inc UL Component Listed: File
MH11826 Vol. 1
Manual Opener Yes
Comments Valve designed for cycling (not constantly powered on)
applications.
Comments Use this valve in closed loop hydronic systems that do not
contain dissolved oxygen in system water, such as fresh water from
frequent source of makeup water.
Literature and other Resources Download
Back To Top
Installation Instructions - (V4044C Diverter Valve)
Product Data - (V4043A, V4043B, V4043E, V4043J, V4044A, V4044B,
V8043A, V8043B, V8043E, V8043F, V8043J, V8044A, V8044B, V8044E
Motorized Valves)
- (V4043, V4044, V8043, V8044 Zone Valve Sticky-Back Labels)
Product Data - (V4044C, V4044F, V8044C, V8044F Motorized Zone Valves,
Valvola Motorizzata Di Zona, Valvulas De Zona Motorizadas)
Download -Submit
Welcome
Category: SUPPLIER DIRECTORY => HONEYWELL, INC
February 2009
> Zone Valves > Valves and Motors > V4044A,B
Residential Comfort/Combustion : Hydronic Heating : Zone Valves and Motors : V4044A,B : V4044A1001/U
Flare Diverting Zone Valve
Overview
On-off and diverting line voltage valves consist of an actuator motor and valve assembly for controlling the flow of hot or chilled water.
Features
- Manual opener (on all models, except straight-through, normally open valves) for valve operation on power failure; valve returns to automatic position when power is restored.
- All models may be installed without disassembling the valve.
- Compact construction for easy installation.
- Complete powerhead may be removed or replaced without breaking plumbing line connections or draining the system.
- Motor may be replaced without removing the valve body or draining the system.
- Suitable for heating and cooling applications.
Product Specifications
- Application
- Hydronic Control
- Dimensions (in.)
- 5 3/8 in. high x 4 11/16 in. wide x 2 3/8 in. deep
- Dimensions (mm)
- 136 mm high x 118 mm wide x 60 mm deep
- Comments
- Use this valve in closed loop hydronic systems that do not contain dissolved oxygen in system water, such as fresh water from frequent source of makeup water. Valve designed for cycling (not constantly powered on) applications.
- Frequency
- 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Listed: File MH11826
- Operating Humidity Range (% RH)
- 5 to 95% relative humidity, non-condensing.
- Voltage
- 120 Vac; Power Consumption--9.6 VA
- Timing
- Nominal Open--30 sec
- Ambient Temperature Range (F)
- 125 F Maximum
- Ambient Temperature Range (C)
- 52 C Maximum
- Connection Type
- Flare
- Body Pattern
- Three-way, Diverting
- Pipe Size (inch)
- 1/2 in.
- Pipe Size (DN)
- DN15
- Current Draw
- 0.08A
- Fluid Temperature (C)
- 5 C to 93 C
- Fluid Temperature (F)
- 40 F to 200 F
- Maximum Differential Pressure Ratings (Close-off) (psi)
- 20 psi
- Maximum Differential Pressure Ratings (Close-off) (kPa)
- 138 kPa
- Electrical Connections (in.)
- 18 in. leads
- Electrical Connections (mm)
- 457 mm leads
- Capacity (Cv)
- 4 Cv
- Capacity (Kv)
- 3.4 Kv
- Valve Action
- Spring Return to port A
- Valve Type
- Zone Valve
- Materials (Body)
- Brass
- Materials (Seat)
- Brass
- Materials (Stem)
- Stainless Steel
- Actuation
- Two position
- De-energized Position
- Port A Normally Closed
- Static Pressure Rating (psi)
- 125 psi
- Static Pressure Rating (kPa)
- 862 kPa
- Materials (Plug/Ball/Disc)
- Buna-N (NBR) Rubber Ball
- Materials (Packing)
- EPDM rubber
- Manual Opener
- Yes