Commercial Building Controls : Building Management Systems : Controllers (Legacy) : T7080 : T7080B1017/U
Electronic Dual Setpoint Thermostat
Overview
Used in W7080 control system to provide modulating space temperature control.
Features
- Separate heat and cool adjustable set point levers provide adjustable deadband from 3 F to 30 F (2 C to 17 C).
- Single 2 to 22 Vdc voltage ramp provides heating/cooling signal to W7080 Load Analyzer.
- Outputs constant 12 Vdc when sensed temperature is within deadband range.
- Ramp output decreases on call for heat: increases on call for cooling.
- C7100B or C7046B Air Temperature Sensors are used to provide heating/cooling anticipation (one required for each zone thermostat) and can also be optionally used as remote return air temperature sensors with the T7080B transmitter.
- Operates on 24 Vdc supplied by W7080A Load Analyzer.
- Mounts on standard 2 x 4 in. outlet box or on nonconductive flat surface.
Product Specifications
- Application
- Packaged RTU; Furnace; Heat Pump Systems; Split System
- Dimensions (in.)
- 4 5/8 in. high x 2 13/16 in. wide x 1 1/4 in. deep
- Dimensions (mm)
- 118 mm high x 71 mm wide x 32 mm deep
- Application Size
- 3 Heat / 3 Cool
- Control System
- W7080 control system
- Output Type
- Voltage Ramp
- Voltage
- 24 Vdc
- Setpoint Temperature Range (C)
- 13 C to 29 C
- Setpoint Temperature Range (F)
- 55 F to 85 F
- Shipping and Storage Temperature Range (F)
- -40 F to +150 F
- Shipping and Storage Temperature Range (C)
- -40 C to +65 C
- Approvals, Department of Defense Guidelines
- Meets
- Approvals, ASHRAE Guidelines
- Meets ASHRAE 90-75