Commercial Building Controls : Standalone Controllers : Temperature Controllers : T678 : T678A1692/U
Remote Temp Control, 15C-75C Range, 2 SPDT, Copper Bulb, 1.5 m Capillary, 2C Diff., Celsius Scale
Overview
Remote bulb thermostats regulate temperature of air or liquids in ducts, pipes, tanks and boilers.
Features
- Suitable for applications requiring temperature control of air or liquids where controller must be placed outside the sensing area.
- Typical uses include control of dampers and valves in heating, cooling and heating-cooling systems.
- Fast response models (available for use in return air duct) operate approximately four times faster than standard models.
- Controller can be mounted in any position. Ambient temperature compensation provides good temperature control.
- Refer to T775 Electronic Remote Temperature Controller where more exact control is required and/or remote controller location is preferred.
- T678 models have a maximum connected load of 2000 VA.
Product Specifications
- Application
- Regulates temperature of air or liquids in ducts, pipes, tanks and boilers
- Dimensions (in.)
- 5 5/8 in. high x 2 in. wide x 2 5/8 in. deep
- Dimensions (mm)
- 143 mm high x 51 mm wide x 67 mm deep
- Comments
- Celsius model; maximum connected load = 2000VA
- Item Type
- Product
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Listed: E4436, Vol. 4, Sec. 11, Guide XAPX
- Approvals, CSA
- Certified: File No. LR95329-1
- Tradeline Value
- Tradeline
- Contact Ratings
- 120 Vac-- 8.0 AFL, 48.0 ALR; 240 Vac-- 5.1 AFL, 30.6 ALR; 277 Vac--4.2 AFL, 25.2 ALR
- Voltage
- 120 Vac or 240/277 Vac
- Setpoint Temperature Range (C)
- 15 C to 75 C
- Operating Temperature Range (F)
- 200 F Maximum
- Operating Temperature Range (C)
- 93 C Maximum
- Type
- Remote bulb
- Output
- relay
- Relay Outputs
- 2 SPDT switch contacts
- Sensor Inputs
- 1
- Sensor Element
- Copper bulb
- Capillary Length (ft)
- 5 ft
- Capillary Length (m)
- 1.5 m
- Bulb Size (in.)
- 1/2 in. x 4 in.
- Bulb Size (mm)
- 13 mm diameter x 102 mm long
- Differential Temperature (F)
- 3.6 F
- Differential Temperature (C)
- 2.0 C
- Interstage Differential Temperature (C)
- 2.0 C to 6.7 C
- Interstage Differential Temperature (F)
- 3.6 F to 12 F