Commercial Building Controls : Standalone Controllers : Temperature Controllers : T678 : T678A1163/U
Remote Temp Control, -15C-+35C Range, 2 SPDT, Copper Bulb, 6.1 m Capillary, Switch: 1.7C Fixed/Interstage: 1.7C-5.6C Adj., Celsius Scale
Overview
Remote bulb thermostats regulate temperature of air or liquids in ducts, pipes, tanks and boilers.
Features
- Suitable for applications requiring temperature control of air or liquids where controller must be placed outside the sensing area.
- Typical uses include control of dampers and valves in heating, cooling and heating-cooling systems.
- Fast response models (available for use in return air duct) operate approximately four times faster than standard models.
- Controller can be mounted in any position. Ambient temperature compensation provides good temperature control.
- Refer to T775 Electronic Remote Temperature Controller where more exact control is required and/or remote controller location is preferred.
- T678 models have a maximum connected load of 2000 VA.
Product Specifications
- Hazmat Information
- UN 1993 Flammable liquid, n.o.s.
- Application
- Regulates temperature of air or liquids in ducts, pipes, tanks and boilers
- Dimensions (in.)
- 5 5/8 in. high x 2 in. wide x 2 5/8 in. deep
- Dimensions (mm)
- 143 mm high x 51 mm wide x 67 mm deep
- Comments
- Celsius model; maximum connected load = 2000VA
- Item Type
- Product
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Listed: E4436, Vol. 4, Sec. 11, Guide XAPX
- Approvals, CSA
- CSA Listed: Report -1
- Contact Ratings
- 120 Vac-- 8.0 AFL, 48.0 ALR; 240 Vac-- 5.1 AFL, 30.6 ALR; 277 Vac--4.2 AFL, 25.2 ALR
- Voltage
- 120 Vac or 240/277 Vac
- Setpoint Temperature Range (C)
- -15 C to +35 C
- Setpoint Temperature Range (F)
- 5 F to 95 F
- Operating Temperature Range (F)
- 125 F Maximum
- Operating Temperature Range (C)
- 52 C Maximum
- Type
- Remote bulb
- Output
- relay
- Relay Outputs
- 2 SPDT switch contacts
- Sensor Inputs
- 1
- Sensor Element
- Copper bulb
- Capillary Length (ft)
- 20 ft
- Capillary Length (m)
- 6.1 m
- Bulb Size (in.)
- 1/2 in. x 4 3/16 in.
- Bulb Size (mm)
- 13 mm dia. x 106 mm long
- Differential Temperature (F)
- 3 F fixed
- Differential Temperature (C)
- 1.7 C fixed
- Interstage Differential Temperature (C)
- 1.7 C to 5.6 C adjustable
- Interstage Differential Temperature (F)
- 3 F to 10 F adjustable