Commercial Building Controls : Standalone Controllers : Temperature Controllers : T675A,B : T675A1102/U
Remote Temperature Controller, 160F to 260F Set Point, 1 SPDT, Copper Bulb, 20 ft. Capillary Length, 3F to 10F Differential
Overview
Remote bulb thermostats regulate temperature of air or liquids in ducts, pipes, tanks and boilers.
Features
- Suitable for applications requiring temperature control of air or liquids where controller must be placed outside the sensing area.
- Typical uses include control of dampers and valves in heating, cooling and heating-cooling systems.
- Fast response models (available for use in return air duct) operate approximately four times faster than standard models.
- Controller can be mounted in any position.
- Ambient temperature compensation provides good temperature control.
- Refer to T775 Electronic Remote Temperature Controller where more exact control is required and/or remote controller location is preferred.
- T675A models with fixed differential have an electrical rating of 125 VA at 120/208/240 and 277 Vac.
- T675B models have 125 VA pilot duty up to 277 Vac.
- T678 models have a maximum connected load of 2000 VA.
Product Specifications
- Application
- Regulates temperature of air or liquids in ducts, pipes, tanks and boilers
- Dimensions (in.)
- 5 5/8 in. high x 2 in. wide x 2 5/8 in. deep
- Dimensions (mm)
- 143 mm high x 51 mm wide x 67 mm deep
- Item Type
- Product
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Listed: E4436, Vol. 4, Sec. 11, Guide XAPX
- Approvals, CSA
- CSA Listed: Report -1
- Contact Ratings
- 120 Vac-- 8.0 AFL, 48.0 ALR; 240 Vac-- 5.1 AFL, 30.6 ALR; 277 Vac--4.2 AFL, 25.2 ALR
- Voltage
- 120 Vac or 240/277 Vac
- Setpoint Temperature Range (C)
- 71 C to 127 C
- Setpoint Temperature Range (F)
- 160 F to 260 F
- Operating Temperature Range (F)
- 280 F Maximum
- Operating Temperature Range (C)
- 138 C Maximum
- Type
- Remote bulb
- Output
- relay
- Relay Outputs
- 1 SPDT
- Sensor Inputs
- 1
- Sensor Element
- Copper bulb
- Capillary Length (ft)
- 20 ft
- Capillary Length (m)
- 6.1 m
- Bulb Size (in.)
- 1/2 in. x 4 3/16 in.
- Bulb Size (mm)
- 13 mm dia. x 106 mm long
- Differential Temperature (F)
- 3 F to 10 F
- Differential Temperature (C)
- 1.7 C to 5.6 C