Product Specifications | |
|
Description | Electronic Pneumatic Transducer with direct action an 2 to 10 vdc input signal |
Application | Electric to pneumatic Transducer |
Maximum Operating Pressure (psi) | 30 psi |
Maximum Operating Pressure (kPa) | 205 kPa |
Output Pressure Range (psi) | 3 to 15 psi |
Output Pressure Range (kPa) | 21 to 103 kPa |
Connections | Dual barb-fittings for 1/4 in. or 5/32 in. O.D. |
Electrical Connections | screw terminals for 14 to 22 gage wire |
Dimensions (in.) | 2 7/16 in. wide x 3 3/8 in. high x 1 7/8 in. deep |
Dimensions (mm) | 62 mm wide x 86 mm high x 48 mm deep |
Airflow Usage | 0.025 scfm (117mL/s) |
Capacity | 0.45 scfm (211 mL/s) |
Maximum Operating Temperature (F) | 131 F |
Maximum Operating Temperature (C) | 55 C |
Nominal High End (psi) | 16 psi with 18 psi main pressure at 12 Vdc or 16 psi at 11 Vdc ( min. ) |
Nominal High End (kPa) | 116 kPa with 125 kPa main pressure at 12 Vdc or 110 kPa at 11 Vdc ( min. ) |
Nominal Low End (psi) | 0.5 psi at 0 Vdc |
Nominal Low End (kPa) | 3.5 kPa at 0 Vdc |
Pressure Range (psi) | 0 to 18 psi |
Pressure Range (kPa) | 0 to 125 kPa |
Voltage | Powered by Control signal |
Operating Humidity Range (% RH) | 5 to 95% RH |
Includes | Without cover, without internal power supply for panel mounting (2 wire) |
|
Keywords: HONEYW HON RP7517A1017 RP7517A1017 HONEYWELL, INC 085267083188 ELECTRONIC - PNEUMATIC TRANSDUCER POWERED BY CONTROL SIGNAL, SCREW TERMI...
Category: [0] => SUPPLIER DIRECTORY => HONEYWELL, INC => HONEYWELL THERMOSTATS, ELECTRIC, VALVES, PARTS, ETC SECTION 22
[1] => SUPPLIER DIRECTORY => HONEYWELL, INC => HONEYWELL REPLACEMENT PARTS => Honeywell Pneumatic Transducers => SUPPLIER DIRECTORY => HONEYWELL, INC => HONEYWELL THERMOSTATS, ELECTRIC, VALVES, PARTS, ETC SECTION 22
Commercial Building Controls : Pneumatic Products : Pneumatic Transducers : RP7517 : RP7517A1017
Electronic Pneumatic Transducer
Overview
Electronic-Pneumatic Transducers are used in electronic-pneumatic control systems to convert a proportional electric output signal from a controller into a direct-acting, proportional pneumatic signal.
Features
- Screw mounting or snap rail (models with cover).
- Factory calibrated.
- Dual barb fittings.
- High accuracy.
Product Specifications
- Application
- Electric to pneumatic Transducer
- Airflow Usage
- 0.025 scfm (117mL/s)
- Dimensions (in.)
- 2 7/16 in. wide x 3 3/8 in. high x 1 7/8 in. deep
- Dimensions (mm)
- 62 mm wide x 86 mm high x 48 mm deep
- Maximum Safe Operating Pressure (psi)
- 30 psi, maximum
- Maximum Safe Operating Pressure (kPa)
- 205 kPa, maximum
- Temperature Range (F)
- 131 F, maximum
- Temperature Range (C)
- 55 C, maximum
- Includes
- Without cover, without internal power supply for panel mounting (2 wire)
- Electrical Connections
- screw terminals for 14 to 22 gage wire
- Operating Humidity Range (% RH)
- 5 to 95% RH
- Voltage
- Powered by Control signal
- Pressure Range (psi)
- 0 to 18 psi; Output--3 to 15 psi
- Pressure Range (kPa)
- 0 to 125 kPa; Output--21 to 103 kPa
- Input Signal
- 2 to 10 Vdc
- Air connections
- Dual barb-fittings for 1/4 in. or 5/32 in. O.D. plastic tubing
- Capacity
- 0.45 scfm (211 mL/s)
- Nominal High End (psi)
- 16 psi with 18 psi main pressure at 12 Vdc or 16 psi at 11 Vdc ( min. )
- Nominal High End (kPa)
- 116 kPa with 125 kPa main pressure at 12 Vdc or 110 kPa at 11 Vdc ( min. )
- Nominal Low End (psi)
- 0.5 psi at 0 Vdc
- Nominal Low End (kPa)
- 3.5 kPa at 0 Vdc
- Current
- 16 mA