Commercial Building Controls : Pneumatic Products : Pneumatic Switches : P658 : P658F1000/U
Panel Mounted Pneumatic / Electric Switch. No Factory Calibration.
Overview
Pneumatic-electric switches convert a controller's pneumatic signal to electrical switching, providing start and stop control. Replacements available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell pneumatic/ electric switches.
Features
- Models available for surface or panel mounting.
- Barb protected by open cage.
- All ferrous parts plated to prevent corrosion.
- Factory calibrated setpoint field adjustable to meet job requirements.
- Neoprene diaphragm element.
Product Specifications
- Application
- Pneumatic / Electric Switch
- Dimensions (in.)
- 3 1/4 in. high x 2 7/8 in. wide x 1 1/2 in. deep
- Dimensions (mm)
- 83 mm high x 73 mm wide x 38 mm deep
- Maximum Safe Operating Pressure (psi)
- 30 psi, maximum
- Maximum Safe Operating Pressure (kPa)
- 207 kPa, maximum
- Temperature Range (F)
- 40 F to 140 F
- Temperature Range (C)
- 4 C to 60 C
- Comments
- No Factory Calibration
- Mounting
- Panel, through double D hole secured with hex nut
- Frequency
- 60 Hz
- Approvals, Underwriters Laboratories Inc.
- Category SDFY or SDFY2
- Electrical Connections
- 1/4 in. quick-connect male terminals
- Operating Humidity Range (% RH)
- 5 to 95% RH, 80 F (27C) max wet bulb
- Approvals, Canadian Underwriters Laboratories Inc.
- Listed, Volume I
- Differential Pressure Range (psi)
- 1 psi
- Differential Pressure Range (kPa)
- 7 kPa
- Switch Operation
- Converts pneumatic signal to electrical switching action (SPDT)
- Switching Action
- Make COM-NO on pressure rise to setpoint plus differential,Make COM-NC on pressure fall to setpoint
- Pilot Duty Ratings
- 720 VA @ 125, 250 or 277 Vac
- Switch Type
- Pneumatic/Electric Switch
- Air connections
- Barb fitting for 1/4 in. (6 mm) O.D. plastic tubing
- Setpoint Range (psi)
- Field Adjustable--2 to 17 psi
- Setpoint Range (kPa)
- Field Adjustable--14 to 117 kPa
- Motor Load
- 3/4 hp @ 125, 250 or 277 Vac
- Resistive Load
- 25A @ 125, 250 or 277 Vac; 10A @ 480 Vac