Residential Comfort/Combustion : Combustion Controls : Fan and Limit Controls : L4029 : L4029E1029/U
Limit control with a fixed 200 F range, manual reset, and a 3 in. insertion
Overview
L4029E Reset Limit Control opens a line or low voltage circuit if the air temperature reaches a critical level. L4029E acts as a fire thermostat in the ducts of AC & ventilating systems. If the air temperature indicates a fire, the fan is shut down.
Features
- Shuts off the fan when air temperature is indicative of fire.
- Internal snap-acting switch actuated by a bimetal strip inserted directly into the air stream responds rapidly to temperature changes.
- Requires manual reset.
Product Specifications
- Dimensions (in.)
- 3 3/4 in. high x 2 5/16 in. wide x 2 in. deep excluding element.
- Dimensions (mm)
- 95 mm high x 59 mm wide x 51 mm deep excluding element.
- Electrical Ratings
- Limit- (AFL)-- 2 A @ 30 Vac: 10 A @ 120 Vac: 5 A @ 240 Vac; Limit- (ALR)-- 60 A @ 120 Vac: 30 A @ 240 Vac
- Approvals, Underwriters Laboratories Inc.
- Listed: File No. MP466, Vol. 8, Guide No. MBPR2
- Approvals, CSA
- Certified: File No. LR95329-5
- Temperature Ratings (C)
- Maximum Ambient-- At switch 88 C: At element: 177 C
- Temperature Ratings (F)
- Maximum Ambient-- At switch: 190 F: At element: 350 F; High Limit Stop-- 200 F
- Switching Action
- Normally closed SPST switch opens on temperature rise to the set point. Switch must be manually reset to operate.
- Element Insertion Length (in.)
- 3 in.
- Element Insertion Length (mm)
- 76 mm
- Pilot Duty Ratings
- 0.25 A @ 0.25 to 12 Vdc