KSCdirect

Product Data

KSCdirect Part #: HON HVFDSD3A0150G200/U
Description: SMARTVFD HVAC 15 HP 208-230 VAC NEMA 12
MFG Part #: HVFDSD3A0150G200/U
UPC: 085267339155
Supplier: HONEYWELL
Please use Live Chat or call 800-918-8939 for exact lead time.

Your Price: $1806.94 / EA

QTY:  
For shipping rates, add item to cart.
* Quantity discounts may be available. Call Kelly Supply at 800-918-8939.
Alternatively, you may e-mail info@kscdirect.com for service.

Details

SMARTVFD HVAC,15 HP,208-230 Vac, NEMA 12,Drive Alone
Commercial Building Controls : Variable Frequency Drives : SmartVFD HVAC : SmartVFD Drives : HVFDSD3A0150G200/U

SmartVFD HVAC, 208/230 Vac, 15 HP, NEMA 12 Enclosure, Drive Alone

Overview

The Honeywell SmartVFD HVAC and BYPASS are designed for commercial buildings to deliver the energy savings that building owners and managers need. Efficient install, and commissioning, in a full featured VFD.

Features

  • Start-up WizardsAll you have to do is tell the VFD whether you have a pump or a fan, enter nominal motor information, and you are up and running.
  • Graphic InterfaceThe easy-to-use keypad and interface deliver menu-driven programming and monitoring for fast, uniform commissioning. It's also easy for the building owner or manager to learn and use, helping to reduce service calls. Plus, a manual is built into the keypad for easy access when needed.
  • Built-in CommunicationsWith BACnet, N2 and Modbus built in, your customers will enjoy a lower total installed cost and reliable communications with the building management system.
  • PC Software WizardsCommissioning, programming and troubleshooting are all a snap thanks to these guided Startup and PID wizards.
  • Built-in PLCAnother reason why SmartVFD HVAC is a great value for your customer, the built-in PLC eliminates the need for an expensive external controller.
  • DC Choke for harmonic protection.
  • Standard RIF FilterEnsures that EMC/RFI requirements are met.
  • Bypass OptionsMeets specifications and system critical applications with a comprehensive bypass offering.
  • Real-Time ClockBattery included.
  • Fire Mode for safe operation.
  • Motor Switch Ride-Through--easy, fault-free maintenance.

Product Specifications

Dimensions (in.)
7.7 x 21.9 x 9
Dimensions (mm)
195.58 x 556.26 x228.6
Weight (lb)
44.1
Weight (kg)
20
Item Type
Product
Frequency
0 Hz to 320 Hz
Voltage
208 Vac; 230 Vac
Operating Temperature Range (F)
14 F to 122 F
Operating Temperature Range (C)
-10 C to 50 C
Enclosure
NEMA 12
Relay Outputs
Max. switching load: 250Vac/2A or 250Vdc/0,4A
Horsepower
15 HP
Current Ratings
48A
Analog Current Output
0 (4) - 20 mA, max 500 ohm
Bypass
Drive alone
Auto Bypass
No
Drive Family
SmartVFD HVAC
Drive Input Disconnect
No
Type of RFI Filter
EMC Filter
Continuous Output Current
overload 1.5 x High overload current (1min/10min); overload 1.1 x Low overload current (1min/10min)
Peak Current
2 x IN, 2 seconds every 20 second period
Acceleration time
0.1 - 3000 sec
Deceleration time
.1 - 3000 sec
Analog Voltage Input
0 - 10 Vdc , 200K ohm
Analog Current Input
0 (4) - 20 mA, 250 ohm differential
Digital Output
Open collector, max. load 48V/50mA
Reference Output Voltage
Maximum Load 10mA
Auxiliary Voltage
20%, max. load 50 mA
Frame Type
6

Attributes/Specifications

Category Commercial Building Controls
Manufacturer HONEYWELL
Product Variable Frequency Drives
Style Variable Frequency Drives

Supplemental Files