Commercial Building Controls : Lighting Solutions : Lighting Controls : CR7075 : CR7075A1000/U
Two-stage photocell lighting controller
Overview
Two-Stage Lighting Controllers offer on/off sequenced control of two separate lighting banks, based on user determined, ambient light intensity level, via a single sensor. Typical applications include, outdoor cosmetic and parking lot lighting.
Features
- Light intensity threshold levels field-adjustable by user.
- Independent Time of Day (TOD) override inputs.
- Optimum start/stop of lighting loads.
- Tamper-proof cover.
- LED annunciation for power on and relay state.
- Wide ambient temperature range.
- Up to 1000-foot separation between photocell and controller.
Product Specifications
- Application
- Two-stage photocell lighting controller
- Dimensions (in.)
- 5 5/16 in. high x 4 9/16 in. wide x 2 1/4 in. deep
- Dimensions (mm)
- 135 mm high x 116 mm wide x 57 mm deep
- Includes
- C7057A1000 Sensor
- Comments
- Adjustment: 2 foot-candles to 80-foot candles. Application: Two-stage independent lighting control
- Item Type
- Product
- Mounting
-
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- File: E87741
- Approvals, CSA
- Certified: File No. LR95329-3
- Output Ratings
- 120 Vac: 9.8 AFL, 58.8 ALR; 240 Vac: 4.9 AFL, 29.4 ALR; Pilot duty: 125 VA.; Resistive: 10 A @ 240 Vac
- Power Consumption
- 5 VA
- Voltage
- 120 Vac; 240 Vac
- Operating Temperature Range (F)
- -40 F to +140 F
- Operating Temperature Range (C)
- -40 C to +60 C