KSCdirect

Product Data

Inquire for Best Price
* Quantity discounts may be available. Call Kelly Supply at 800-918-8939.
Alternatively, you may e-mail info@kscdirect.com for service.

Details


Commercial Building Controls : Lighting Solutions : Lighting Controls : CR7075 : CR7075A1000/U

Two-stage photocell lighting controller

Overview

Two-Stage Lighting Controllers offer on/off sequenced control of two separate lighting banks, based on user determined, ambient light intensity level, via a single sensor. Typical applications include, outdoor cosmetic and parking lot lighting.

Features

  • Light intensity threshold levels field-adjustable by user.
  • Independent Time of Day (TOD) override inputs.
  • Optimum start/stop of lighting loads.
  • Tamper-proof cover.
  • LED annunciation for power on and relay state.
  • Wide ambient temperature range.
  • Up to 1000-foot separation between photocell and controller.

Product Specifications

Application
Two-stage photocell lighting controller
Dimensions (in.)
5 5/16 in. high x 4 9/16 in. wide x 2 1/4 in. deep
Dimensions (mm)
135 mm high x 116 mm wide x 57 mm deep
Includes
C7057A1000 Sensor
Comments
Adjustment: 2 foot-candles to 80-foot candles. Application: Two-stage independent lighting control
Item Type
Product
Mounting
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
File: E87741
Approvals, CSA
Certified: File No. LR95329-3
Output Ratings
120 Vac: 9.8 AFL, 58.8 ALR; 240 Vac: 4.9 AFL, 29.4 ALR; Pilot duty: 125 VA.; Resistive: 10 A @ 240 Vac
Power Consumption
5 VA
Voltage
120 Vac; 240 Vac
Operating Temperature Range (F)
-40 F to +140 F
Operating Temperature Range (C)
-40 C to +60 C

Attributes/Specifications

Category Commercial Building Controls
Manufacturer HONEYWELL
Product Lighting Solutions
Style Lighting Solutions

Supplemental Files

This item has no supplemental files.