Commercial Building Controls : Pneumatic Products : Pneumatic Velocity Controllers : CP980 : CP980E1060/U
Direct acting Pneu. Velocity Cntrllr,"C"
Overview
An ultra-sensitive air velocity sensor and pneumatic controller, control pneumatic damper actuators in heating and air conditioning systems to provide constant air velocity in the duct regardless of the static pressure.
Features
- State-of-the-art design provides reliable operation.
- Not position sensitive.
- Direct Acting (DA) and Reverse Acting (RA) models are available.
- Insensitive to static pressure changes.
- Accurate control throughout entire velocity range.
- Graduated scales for minimum and maximum velocity adjustments.
- Velocity reset by thermostat demand.
- Adaptable to many terminal unit control strategies.
Product Specifications
- Application
- Velocitrol Air Velocity Sensor
- Airflow Usage
- 0.029 scfm (13.7 mL/s), includes supply for bleed type thermostats for type B, does not include thermostat air for type C controller
- Dimensions (in.)
- Controller: 1 3/4 in. high x 3 1/4 in. wide x 2 3/8 in. deep / Sensor: 3 3/16 in. high x 1 3/4 in. wide x 4 3/16 in. long with orifice and 3 3/8 in. long without orifice
- Dimensions (mm)
- Controller: 44 mm high x 83 mm wide x 60 mm deep / Sensor: 81 mm high x 45 mm wide x 107 mm long with orifice and 86 mm long without orifice.
- Maximum Safe Operating Pressure (psi)
- 30 psi
- Maximum Safe Operating Pressure (kPa)
- 207 kPa
- Temperature Range (F)
- 40 F to 130 F
- Temperature Range (C)
- 5 C to 55 C
- Comments
- For normally open damper and two-pipe thermostat
- Mounting
-
- Approvals, Underwriters Laboratories Inc.
-
- Approvals, CSA
-
- Operating Humidity Range (% RH)
- 5 to 95% RH
- Approvals, Factory Mutual
-
- Sensor Element
- Remote Sensor
- Connection Size (in.)
-
- Differential Pressure Range (psi)
-
- Differential Pressure Range (kPa)
-
- Approvals, NEMA Standard
-
- Pressure Ratings (psi)
- Reset-- 9 to 15 psi
- Pressure Ratings (kPa)
- Reset-- 62 to 103 kPa
- Number of Pipes
-
- Changeover Pressure (psi)
-
- Changeover Pressure (kPa)
-
- Mainline Pressure Range (psi)
- 18 psi Minimum, 20 psi Nominal
- Mainline Pressure Range (kPa)
- 124 kPa Minimum, 138 kPa Nominal
- Capacity
-
- Control Range (fpm)
- 500 fpm up to 3500 fpm by changing orifice
- Control Range (m/s)
- 2.5 m/s up to 17.8 m/s by changing orifice
- Number of Sensor Inputs
-
- Remote Control Point Adjustment
-
- Approximate Throttling Range, Midscale (psi)
-
- Approximate Throttling Range, Midscale (kPa)
-