Commercial Building Controls : Sensors : Temperature Sensors : C7776 : C7776A1006/U
10K ohm NTC Type II Duct Temp Sensor, 6 in.prove/8.5 in.stranded wire, -45-99F
Overview
The C7776 Air Temperature Sensors are direct wired temperature sensors that are used to sense discharge or return air in a duct. The sensors are 10 ohm NTC Type II sensors that are compatible with TB7600, TB7300, and TB7200 communicating thermostats.
Features
- Primary and/or secondary sensor for use with electronic control systems
- Integral 10K ohm NTC Type II nonlinear sensors
- Operating range of 45 to 99 F (7 to 37 C)
- Mounts on a flat duct or plenum surface or, for a plenum-rated application, in a standard utility conduit box
- Probe length of 6 in. (152 mm)
- Rugged 1/4 in. diameter aluminum insertion probe
Product Specifications
- Application
- Primary and/or secondary sensors in electronic control systems
- Dimensions (in.)
- 1 in. high x 2 in. wide x 7 in. deep
- Dimensions (mm)
- 25 mm high x 51 mm wide x 177 mm deep
- Used With
- TB7600, TB7300, TB7200 Series communicating thermostats
- Item Type
- Product
- Mounting
- Mounts on flat duct or plenum surface with integral mounting flange or in a 2 in. x 4 in. (51 mm x 102 mm) junction box.
- Operating Humidity Range (% RH)
- 5 to 95% RH, non-condensing
- Sensor
- 10 K ohm NTC Type II non-linear
- Operating Temperature Range (F)
- 45 F to 99 F
- Operating Temperature Range (C)
- 7 C to 37 C
- Shipping and Storage Temperature Range (F)
- -40 F to +150 F
- Shipping and Storage Temperature Range (C)
- -40 C to +65 C
- Insertion Length (in.)
- 6 in.
- Insertion Length (mm)
- 152 mm